|
Real world suggestions for the residential Service Technician from
Bill Ribble, 40-year Honeywell veteran and controls expert.
By The Numbers - October 2005
edition
This time-worn phrase is familiar to
us and it an appropriate term to apply to the HVAC service business.
Service technicians must be proficient in the use of service tools
and measurement instruments such as multi-meters, U-tubes,
manometers, voltmeters and so on. The proper use of these tools will
enable the technician to professionally diagnose and repair
problems, and do so in a professional manner that earns continued
customer loyalty.
Would you like to know how proficient your techs are at using these
(expensive) tools? At your next service meeting, challenge then with
this short quiz so you can see where your tech’s strengths are, and
where you need additional training.
Mr. Control Pro Quiz: Using Meters on Service Calls
Question #1:
Honeywell intermittent gas ignition devices are the most common
types used among all manufacturers. They recommend that a properly
adjusted pilot – steady, non-wavering – flame should produce (with
main burner off) a flame signal of:
A. .2 amps
B. 132 volts
C. .000002 amps dc
D. 18-30 millivolts
E. 175 ohms
Question #2:
What is the proper output voltage (without a load) of a NEMA rated
120/24 volt AC step down transformer?
A. 24 VAC
B. 26-32 millivolts
C. 120-124 VAC
D. 261/2 +/- ½ VAC
E. 18-32 volts
Question #3:
New, standard purpose single thermocouples, in order to meet code
requirements, must open the main valve circuit in no longer than
_____ (seconds, minutes, hours) on a loss of pilot flame?
A. 180 seconds
B. 15 seconds
C. 2 minutes
D. Right quick
E. 60 seconds
Question #4:
The “cad” cell (oil) output reading on a normally adjusted gun type,
high pressure oil burner should read:
A. 1600 to 2500 ohms
B. 16 to 25 ohms
C. 300 to 1000 ohms
D. 2150 to 2175 ohms
E. 1200 to 1500 ohms
Question #5:
Standard, direct burner ignition, Norton ignitors (silicon carbide)
are typically used on both White Rogers and Honeywell ignition
systems. They are powered with 120 VAC for either _____ or _____
before testing for flame recognition of main burner.
A. 60 seconds or 120 seconds
B. 17 seconds or 34 seconds
C. 4 or 7 seconds
D. 3 minutes or 5 minutes
E. 11 minutes or 4 minutes
Correct Answers are:
1. C
2. D
3. A
4. C
5. B
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

By The Numbers - November 2005 edition
The HVAC service business can be a "numbers game". In this month’s
article we’ll take a look at how we can follow the numbers when
servicing or troubleshooting gas burner Intermittent Ignition Systems.
Most systems in use today use the principle of Flame Rectification to
prove the presence of the pilot flame. Here is the typical sequence of
operation:
# 1 - The pilot flame is a conductor of current - just like a copper
wire - except it's resistance is extremely high. When metered, you will
see a natural gas pilot flame measuring on the order of 11 to 12 meg
ohms.
# 2 - The surface area of the flame sensor (flame rod) in the pilot
flame must not exceed 1/4 of the total ground area ( including the pilot
burner hood , pilot burner ground straps , etc.. ). This ratio is
critical in order for an A/C signal to be rectified into a pulsating
D.C. signal .
# 3 - The D.C. signal in the circuit must, in almost every system, equal
or exceed 2 micro-amps (.000002 ) for the control module to operate
properly . A steady signal of 2 or more microamps will produce reliable
operation. A wavering signal (from less than 1 microamp to 2,3,4 5, or
more ) will produce nuisance shutdowns. These signals are generally
caused by drafts across the pilot flame or main burner flame impingement
on the pilot burner assembly. A drop in signal strength below 1.6
microamps for .8 of a second will cause nuisance shutdowns or lockouts.
A high percentage of those systems operating today will automatically
recycle after 5 minutes however older systems require manual resetting.
This can be done by either killing power to the system transformer or
lowering the room temperature on the thermostat for approximately 1
minute before resetting it to the normal temperature.
#4 - Other areas of concern are :
A - Cracked ceramic flame rod holders
B - Bent or misaligned pilot burner brackets
C - Partially clogged pilot orifices or main gas valve filters
D - Contaminate build-up on flame sensors
E - Shorts in the flame sense circuit caused by scale from the heat
exchanger or main burner
Probably the most common problem is a BAD GROUND CONNECTION TO THE
SYSTEM. QUICKLY CHECK THIS BY CONNECTING A JUMPER WIRE FROM THE PILOT
BURNER BRACKET TO THE BURNER GROUND CIRCUIT CONNECTOR ON THE SYSTEM
MODULE. IF THE SYSTEM FUNCTIONS NORMALLY, YOU SIMPLY NEED TO PROVIDE A
BETTER PERMANENT GROUND.
This is a " Readers Digest " version of just some of the numbers your
techs need to be familiar with in order to service Intermittent Ignition
Systems in the field today.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

By The Numbers - December 2005
edition
Smart Valve Gas Ignition Systems #1
This month’s article will be the first of several that will deal
with the specifics of numerous varieties of the "Smart Valve" gas
burner ignition system. In excess of 4.5 million of these systems
are in use today on equipment as diverse as residential gas
furnaces, roof top packages, domestic water heaters and deep frying
equipment built by a large number of different manufacturers.
Smart Valve Gas Ignition System Overview
• All Smart Valves eliminate the need for a separate device,
remotely mounted, that contains the electronics necessary to control
the sequencing of the pilot, the main gas burner and flame sensing
circuit. All of these functions take place in the valve’s operating
head.
• Each of the many varieties of this Smart Valve system use flame
rectification for flame proving .
• All of the system’s electrical wiring occurs on the valve’s top
using Amp-type electrical connectors to plug in to receptacles on
the valve (except on Generation I systems, which have the 4-pin
power receptacle located on the valve’s gas outlet face).
• All of the different low voltage systems use Norton’s 24 VAC type
silicon nitride igniter. This igniter has a low starting resistance
to current flow and it heats to the temperatures needed in +/- 2
seconds. As its temperature rises its resistance increases.
• Smart Valve systems that use line voltage igniters require Norton
igniters that need from 7 to 17 seconds for proper warm-up prior to
allowing main gas to flow. These igniters are a version of silicon
carbide. These have a higher initial resistance to current flow but
it reduces as it heats .
• All valves (with exception of Generation 1 valves) have an
electrical on-off switch located on the valve’s top . This
interrupts current flow to the valve’s pilot and main gas valve. It
is also the replacement for the older style units that utilize gas
rotary shut off gas cocks .
• These systems are not suitable for equipment retrofit on older
appliances. They can only be applied by the appliance manufacturer.
• These systems have a maximum gas capacity of 415 cfh - depending
on the valves inlet and outlet sizes. It is important to note the
valve’s capacity must be reduced by 5% if a screen-type filter is
used in the outlet of the valve .
• Basic versions will provide a communications link to the equipment
's electronic fan timer to start the "Start-On delay and Fan-Off
delay" timings. This signal is provided through a 16 VAC signal to
the EFT carried by a lead in the 4-pin plug that supplies the 24 VAC
power to the valve from the EFT.
These are but a few of the unique system properties that must be
understood by your technicians so that they may provide excellent
service to your customers that own equipment with Smart Valves "
Feel free to email me with any questions you or any of your
co-workers might have.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Pressure Regulating Gas Valves - January 2006
edition
In last months article we reviewed a number of differences between
Honeywell's "Smart Valve" gas ignition control system and
conventional intermittent ignition gas burner control systems.
The techniques and skills used to service Smart Valves are the same
or very similar to those already being used to service standard
systems. This article will focus on the Pressure Regulating Valve (PRV)
components that are part of the gas valve/ignition control system.
The gas pressure regulator's purpose, whether it is a functional
component of the control valve, or a separate entity, must control
the gas pressure (natural or L.P.) to the main gas burner. The gas
utility provides a main (service-pounds to inches) regulator to the
residence or building from which all of the building’s gas needs are
to be met. Generally, the goal is to supply natural gas at 7" water
column (W.C.) at the outlet side of the regulator. On occasion this
may not happen. In extreme cases where the weather is severe and/or
the customer is toward the end of the gas line, the available
pressure, because of capacity issues, may actually be lower than
desired.
Most gas burning appliances are designed to operate on 3.5" W.C. on
natural gas ( 11.0" W.C. on propane). One thing is certain - THE GAS
VALVE REGULATOR CANNOT RAISE THE INLET PRESSURE TO THE MAIN BURNER
ABOVE THE INLET PRESSURE TO THE VALVE. When the technician checks
gas pressures he/she should have all of the buildings appliances
operating at full capacity.
It is important to note that over 95% of all combination gas valves
DO NOT regulate the pressure of the gas to the pilot outlet. When
you adjust the pilot adjusting screw, you are changing the flow rate
- not the pressure - and you are basically changing only the pilot
gas flame size. It is important to keep the pilot flame steady, (not
like a torch) and in constant contact with the pilot burner hood for
good pilot fame recognition in the sensing circuit. The pressure of
the pilot gas will be the pressure of the gas at the valves inlet
minus the pressure drop through the valve. On average, you could see
6.0 to 6.2" W.C. when you have 7.0" at the valves inlet (natural
gas)
Troubleshooting Tips
# 1. - Each valves capacity is partially a function of the valves
inlet and outlet dimensions, and the regulators range of pressures
that it can safely operate. The valves complete model number will
provide the information about its capacity, the regulators range of
pressures it can provide and other special features the valve may
include.
# 2 - Any time you find it necessary to replace a gas valve it is a
good technique to, after replacing the valve, check the outlet
pressure to the main burner, To insure that you do not overfire or
underfire the burner (sooting, not enough capacity to meet the
spaces requirements, tee..) always check the appliance’s rating
plate and check to see the regulator is set correctly.
# 3 - You may change the regulator’s output by removing the cap
screw and repositioning the underscrew. Turn the underscrew
CLOCKWISE for RAISING the set point and turn the underscrew COUNTER
CLOCKWISE to REDUCE the set point.
# 4 - All combination gas valves have outlet pressure taps for
measuring outlet pressures and only Honeywell provides an inlet
pressure tap for ease of getting inlet pressure readings .
#5 - A few valves (including Smart Valves) have outlet screens
(filters) - in such event, these filters will reduce the output
capacity by 5%. Most valves have additional filters imbedded in the
body of the valve to protect the pilot gas passages and these are
not replaceable in the field.
#6 - If the inlet gas pressure to the valve (including Smart Valve)
is in the valves nominal range (consult the valves specification
sheet) and you cannot provide the correct capacity / pressure to the
main burner - you should replace the valve.
Next Month: More on Smart Valves and their control and servicing.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Operating Principles and Troubleshooting of
Honeywell Smart Valve - February 2006
edition
As promised in last month’s Sales Bytes, this issue will focus on
the Operating Principles and Troubleshooting of Honeywell Smart
Valve gas control systems for residential type gas burning
equipment.
Let’s start with the Operating Sequence.
The operating sequence of Smart Valve gas ignition and control
systems is very similar to the older style, intermittent ignition
systems which incorporate remotely mounted spark ignition modules.
Those older systems use a 12,000 to18, 000 DC voltage source for
ignition of the pilot gas. The Smart Valve system uses a 24 VAC
powered hot surface pilot gas igniter to ignite the pilot gas. The
main gas is ignited in both instances by a pilot gas burner.
The Smart Valve system is self-contained, thus eliminating the need
for a separately mounted ignition source, usually in the furnace or
boiler vestibule.
Starting with a call for heat from the thermostat, the circuit
usually (not always) will be completed to the R and W terminals
located on an Electronic Fan Timer (EFT). A separately mounted
120/24 VAC transformer supplies power to the entire control circuit.
Immediately the EFT energizes the induced draft fan. As quickly as
the Air Proving Switch (APS) senses that there is a proper amount of
draft air moving through the combustion chamber, the APS closes its
switching contacts in order to complete the circuit to the Smart
Valve. As the circuit is completed, the igniter is powered and the
pilot gas valve is opened with the igniter lighting the pilot gas.
In those systems using an EFT the Smart Valve sends a 16 VAC signal
to the EFT to start the time delay which dictates the amount of time
that must pass prior to energizing the air handling blower.
The flame rectification / proving system proves the pilot flame is
lit (in less than 2 seconds) and allows the main fuel valve to open
and to simultaneously shut down the igniter. The flame proving
system continues, monitoring only the pilot gas flame. The main fuel
valve remains open until the call for heat ends. In those instances
where some problem exists, the operation includes a 90 second Timed
Trial for Ignition. If the system has not proven the pilot flame in
90 seconds of trying to prove the pilot, the system will shut down
(not lockout) for 5 minutes and then will go through the starting
sequence again. The system will go through this sequence until
either the call for heat is ended or the burner lights off
successfully.
Once the call for heat is completed, the EFT starts the timing cycle
(field adjustable) to allow the air handler to complete the
blower-on timing.
The above sequence applies to SV9X00 and the SV9X01. The SV9X02
includes a pre-purge timing (15 or 30 seconds) and the SV9X03
includes a lockout after one attempt to light-off.
TROUBLESHOOTING SMART VALVE SYSTEMS
The steps to correctly troubleshoot Smart Valves are as follows:
#1 - Shut off the flow of gas to the appliance in question with the
' A ' cock.
#2 - Make certain that the gas cock, located on top of the SV9X00
family of Smart Valves or later generations of Smart Valves SV9X01,
SV9X02, SV9X03 which include an electrical slide switch (replaces
the rotary gas cock) are placed in the Open or on position.
# 3 - Unplug the 2 x2 system harness plug located on top of the
valve operating head.
# 4 - Make certain there is 24 VAC available from the system’s
control circuit transformer. The transformer MUST be a minimum 40 VA
(NEMA) rated. Such systems as SV96XX must have 50 VA NEMA-rated
transformers at a minimum.
# 5 - Measure for output voltage at the 2 x 2 connector for 24 VAC
between the 24 VAC common connector pin (Locate the proper pin
locations in the Smart Valve instruction sheet) and the 24 VAC power
source pin from the thermostat and/or air proving switch. There
should also be 24 VAC between the 24 VAC common connector pin and
the 24 VAC connector pin. (Note - there must be 2 pins powered for
the system to operate. (One is constantly powered and one powered
through the thermostat and/or air pressure switch).
# 6 - Plug the 2 x 2 wiring plug to the 2 x 2 wiring receptor. With
24 VAC present on the 2 receptacle pins the system will be
energized. A 2-3 second delay will occur in the start up to allow
the system to self check its electronics for a flame simulating
component failure (If a component should have failed it will not
continue to operate.)
After this delay the ignition sequence will begin in the SV9X01 and
SV9X03 systems. The SV 9X02 has a pre-purge delay of either 15 or 30
seconds - OEM's choice.)
#7 - The silicon nitride 24 VAC igniter should begin to heat and in
1 to 2 seconds glow red. If the igniter fails to glow to
incandescence and you have the proper voltage present (19.5 - 26 VAC)
- replace the igniter if the nominal voltage is not present to the
igniter - replace the Smart Valve.
# 8 - If the igniter, which is part of the pilot burner assembly
(Q3450 or Q3480) glows red, turn the main gas supply gas cock back
to the open position. The pilot gas should ignite. If not confirm
that gas is present in the piping system, that all of the air has
been purged from the pilot gas line (all the air must purge the
pilot gas orifice.)Make certain a call for heat still exists - if
the pilot gas does not ignite at this point replace the Smart Valve.
Please note that all of the ignition module components are contained
in the gas valve and the entire Smart Valve must be replaced.
If gas flow is present to the igniter and ignition doesn't occur
measure for voltage between the 24 VAC common connector pin and the
24 VAC hot pin. If a nominal 24 VAC (19.5 to 26) is not present
check the 24 VAC transformer output and replace the transformer with
a properly sized, NEMA rated transformer (required for warranty
purposes.) If you have the proper voltage to the igniter and it does
not glow replace the igniter with a replacement igniter/flame rod
assembly Q3400A1024. The igniter and flame rod must be replaced at
the same time - they are combined into a one piece assembly and are
packaged with a new stainless- steel spring mounting clip. This one
unit fits both the Q3450 and Q3480 pilot burners.
# 9 - If the main burner does not light after the pilot has ignited
and the igniter has been de-energized:
A. - Make certain that the pilot flame and the flame rod are making
good contact.
B. - Check that the pilot burner bracket is not misaligned or bent
from its original position
C. - Use a gas pressure reading instrument (i.e... Manometer etc...
) to check for proper inlet gas pressure. There is an outlet gas
pressure tap on the outlet side of the gas valve for this
measurement - there is also an inlet pressure tap as well. For
natural gas systems, the pressure required is normally #.5 inches of
water column however check the appliances Manufacturers rating plate
to verify the pressure needed on this unit for correct firing
D. - Inspect the pilot orifice or clogging or apparent damage. If
necessary, replace the orifice - DO NOT attempt to drill out the
orifice.
E. - Check the electrical system for a good system ground through
the pilot burner gas tubing ' You can use a jumper cable (with
alligator clips). Connect one end of the cable to the pilot burner
bracket and the other end to the gas valve - if the system then
operates, you have isolated the problem to a bad or insufficient
ground.
F. - If none of these checks surfaces the system problem then
replace the ignition assembly (Q 3400 a 1024) At this point the
system should operate properly - if not - replace the Smart Valve.
TROUBLE-SHOOTING TIPS.
To correctly diagnose system problems in Smart Valve products you
should have a digital multi-meter or a analog meter - either of
which should be able to measure one tenth of a micro amp ( .0000001
amps / dc. )The meter should also read ohms resistance down to one
tenth of one Ohm (.01)
AA. - The resistance of a Norton silicon igniter used in the Q3450
or Q 3480 pilot assemblies, when new and cold, will be between 3 and
4 Ohms (average 3.7 Ohms) as the igniter ages the resistance will
increase. When its resistance reaches 10 Ohms the igniter should be
replaced
BB.-.A test harness for use in making micro amp readings while the
system is working is available through your Honeywell distributor -
the part number is 395466 .Smart Valves - Generation 1 will need a
minimum reading of .0000003 micro amps (Three tenths of one micro
amp) Generation 1 systems can be easily identified by the rotary gas
cock knob on the top of the valve. It will also have part numbers SV
9500 or SV 9600 Generation 2 systems or later can be identified by
an electrical slide switch on top of the gas valve. This slide
switch electrically opens or closes the gas flow circuit in the
valve and replaces the rotary gas cock. Generation 2 valves are the
direct replacement for both generation 1 and 2 valves .This test
harness also will allow you to easily convert micro amps to
kilovolts. The minimum value you want for a microamp reading on
generation 2 systems is 2 (.000002 A). Most importantly is the need
that the microamp signal, on either system, be a steady signal. A
wavering signal indicates that the pilot flame is not playing on the
flame rod steadily - the flame recognition time is less than 2
seconds - and nuisance shutdowns will occur. Check for drafts across
the pilot burner .
In following issues of Sales Bytes we will discuss older
Intermittent Ignition Systems.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Operating Principles and Troubleshooting of
Older Intermittent Ignition Systems - March 2006
edition
In last month’s Sales Bytes, we
focused on the Operating Principles and Troubleshooting of Honeywell
Smart Valve gas control systems for residential type gas burning
equipment. Now we’ll look at older Intermittent Ignition Systems.
There are in excess of 24 million electronic intermittent ignition
controls systems in operation today. Each uses a separate ignition
module remotely mounted in the appliance. Its job is to sequence the
source of ignition and control the main fuel valve. Honeywell, in
both OEM as well as the trade version for universal replacement, has
historically provided the bulk of these units to the residential and
light commercial markets.
The most significant difference in troubleshooting these ignition
systems is in the flame sensing circuit. Once that is mastered,
troubleshooting the rest of the system is very similar to even older
standing pilot systems.
To illustrate what you need to do we’ll use the Honeywell S8610U
intermittent ignition control module. This is a universal control
module that will replace over 300 Honeywell and competitive devices.
This package includes the module, valve, ignition hardware and
cables necessary for the complete replacement.
Troubleshooting Honeywell’s S8610U Ignition Control System
1. Turn off the power supply to the appliance. Set the
thermostat to call for heat. Check for 24 VAC to the module. You’ll
need to check at the TH-TW terminal and at the 24 VAC terminal if an
automatic vent damper is installed to the damper connector.
a. If POWER IS NOT PRESENT check the low voltage transformer output,
then the limit contact for closure, then the thermostat to confirm
it is calling for heat. You may also need to check any air proving
switch(s), the vent damper (confirm it is open), and that the vent
damper end switch is closed.
b. If POWER IS PRESENT then check for a spark across the igniter /
sensor gap. If there is NO SPARK, pull the ignition lead and check
for spark at the ignition stud or terminal. Vent Damper Alert: Make
certain that a vent damper had NOT previously been installed and
cycled. There is an ANSI standard that required an internal fuse to
open when that happened to ensure that, in that case, the vent
damper was always installed and operating properly.
c. If a SPARK IS PRESENT when you test at the stud / terminal:
i. Check the ignition cable, ground wiring, the ceramic insulator
and the gap on the ignitor (should be .125 inches). If in doubt,
replace the component.
d. If SPARK IS PRESENT when you initially check the ignitor gap and
then it stops, turn off the gas supply and start the sequence over
again.
2. Does the pilot burner light?
a. If the PILOT DOES NOT LIGHT then check all the manual gas valves
are open, that the supply tubing is not kinked, that inlet pressures
are good and that the pilot burner orifice is not plugged.
b. Also check the electrical wiring to the gas valve’s pilot
terminal (PV). You should see 24 VAC across the PV-MV/PV terminal on
the module. If OK, replace the gas valve. If NOT OK replace the
S8610 module.
c. When the pilot burner lights, does the spark shut down? If the
spark DOES NOT SHUT DOWN check the ignition cable’s continuity and
the ground contacts.
i. Connect a jumper cable between Terminals 4 and the pilot burner
bracket. If the system works correctly then the problem is a bad
ground. A 2 microamp signal (steady) is the minimum you want to see.
d. Flame rods need to be clean. Use s very, very fine burnishing
cloth to clean them if needed.
e. Check for cracked ceramics. This will eventually cause a leak to
ground.
f. Adjust the pilot flame so that it covers the flame rod and is
steady and blue. The flame must be shielded from any drafts.
g. If the SPARK SHUTS DOWN WHEN THE PILOT LIGHTS does the main
burner light? If the main burner does not light check for 24 VAC
across the MV-MV/PV terminals. If power is present, replace the
valve. If power is not present, replace the module.
3. Other checks
a. High temperature on the ceramic insulator can cause signal
leakage to ground. Temperatures should be less than 1600F.
b. While the system is running remove the cable from the MV
terminal. The gas valve must close. If not remove and replace the
valve.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Questions from the field - April 2006
edition
Some good questions have come to me
this past month and I’d like to share the replies with all of you.
What method do you recommend that we use to measure the micro-amp
circuit value output in older individual component, electronic
intermittent ignition systems?
Several questioners were inquiring about the Honeywell S 8610 family
of electronic ignition systems. First of all, you must use an
accurate ammeter (or multi-meter) that will permit readings in
micro-amps (.000001) the specification sheet for the module you are
testing will generally indicate that a minimum reading of 1.2
microamps is required. This statement is accurate, however, in
actual field installations, a reading of that magnitude will produce
numerous nuisance shut-downs .The reason for that is the " flame
failure response " time is so fast - less than . 8 seconds - that
any thing that can cause the pilot flame to drift, if only
momentarily (drafts, clogged pilot burner orifices, low or
fluctuating gas pressure etc...), will cause the system to go
through the start cycle all over again. The “timed trial for
ignition is 90 seconds. If you have not proven the pilot in that
length of time the system will shut down for 5 minutes and then
restart the cycle all over again. That process will continue until
the thermostat is satisfied or the power is turned off.
When testing the micro-amp signal you should remove the low voltage
lead to the main fuel valve- either on the " MV " terminal on the
gas valve or the ignition module .If you allow the main valve to
operate during the test period the main burner flame may / will
impinge upon the pilot burner bracket / or pilot flame and will
increase the micro-amp output which will give a false reading. While
many pieces of literature will indicate that you may achieve a
reading of up to 10 micro amps this really only happens in the test
labs, I believe. In real world applications, a steady (no wavering
of the pilot flame or fluctuating of the meter reading) 2 to 5
microamps will provide reliable performance
The meter should (like any amp measurement) should be placed in
series with the load. In the case of testing the S8610U module the
meter should be placed in series with the burner ground lead. The
module is labeled “Burner Ground”
The hot surface igniter (HSI) used on direct burner ignition systems
appears similar to the material used in “Smart Valve " systems. The
line voltage igniter normally has a long warm-up time of either 17
or 34 seconds before the main fuel valve may be opened for main
burner light -off. Why does the igniter used with “Smart Valve
“systems light up so quickly in order to ignite the pilot?
The two igniters, while similar in appearance, are made of different
alloys. The Norton igniter models 201 and 271 are made of silicon
carbide while the Norton igniter used in “Smart Valve “low voltage
gas burner ignition systems are comprised of silicon nitride and
additional compounds.
The Norton 201and 271 igniters have line voltage - 120 Vac - applied
to them and they have a high initial resistance to current flow -
thus the long warm - up timing. The resistance reduces as the
igniter warms The Honeywell pilot burner family (Q 3450) used in
“Smart Valve " systems utilize a combination flame rod / igniter in
a fixed bracket that is held in place in the pilot burner bracket
with a stainless spring clip . . If either the fame rod or igniter
must be replaced both must be replaced. The igniter has low initial
resistance to current flow- it heats up quickly - less than 2
seconds- to provide ignition to the pilot gas flow which is
energized at the same time as the igniter is energized .The
resistance value of the igniter - when new and cold will be between
3 and 4 ohms . The resistance of the igniter increases with use and
time. Replace it when the resistance gets to 10... On series 2
“Smart Valves “the minimum micro amp reading should be 2, on series
1 systems the minimum should be .0000003. (.3 micro amps.)
Next month we will review low voltage -step down transformers. -
Application and sizing.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Questions from the field - June 2006
edition
OIL BURNER PRIMARYS
Oil burner primary controllers are classified into
two specific groups - thermal (heat sensing) and optical sensing.
Both of these groups also are separated into two different types of
ignition providing devices - Intermittent Ignition and Interrupted
Ignition.
Intermittent Ignition-- (Previously - pre 1964 were called Constant
Ignition) The igniter is powered when the burner is powered and will
remain energized as long as the burner is powered. The ignition and
the burner normally are powered form the same contact on the primary
control.
Interrupted Ignition -- (Previously - pre 1964 were called
Intermittent -- changes mandated by U.L.) the igniter comes on when
the burner is energized. The igniter will shut down automatically
when flame has been established or after a pre-determined period of
time has elapsed.
Non - Recycling control. - Upon a loss of flame the controller will
try to restart the burner for the length of timing on the safety
switch
Recycling control - the controller will shut down the burner
immediately on loss of flame and will attempt to restart the burner
once before the control will lock out on safety.
Thermal Sensing Systems --
While neither any oil burner manufacturer or equipment manufacturer
has shipped a thermal sensing (one or two piece) oil burner primary
with a piece of equipment since 1962/1963 there are several hundred
thousand furnaces or boilers in operation today using these older
style controllers for burner operation - witness the fact that
Honeywell still provides NEW (not rebuilt) for replacement purposes.
These primary controls are usually mounted in the elbow of the
“stack” (whether one or two piece controller). The tube containing
the sensing element - ( thermal sensor - usually a " U " shaped
bi-metal -) is mounted ahead of the barometric control and
positioned so that the sensor is located in the path of the hottest
flue gases usually the outer radius of the stack .The sensing
element should not be exposed to temperatures hotter than 1000
degrees " F " . The element can be permanently distorted.
Furthermore, periodic service should include cleaning the “bi-metal.
It should be dirt and soot free for proper temperature sensing.
Coating the sensor will slow ( inhibit ) the sensor from responding
( expanding longitudinally ) to a temperature rise or fall in the
flue gas .On an increase in stack temperature the bi- metal
straightens and moves the drive shaft towards the cover end of the
control. This outward movement of the drive shaft causes the "
clutch fingers " to open and close the " hot and cold " contacts
.The clutch fingers ride on the drive shaft and they must be able to
freely slide on the drive shaft, however, there must be enough
friction between the drive shaft and the clutch fingers so that the
drive shaft can cause the " hot and cold " contacts to open and
close in the proper operating sequence.
Honeywell's RA116, RA816 and C550 have only one set of contacts and
they act as both the hot and cold contacts. Their RA 117 and RA 817
have two sets of contacts.
Stack Relay Operation - RA 116 and RA 816 style controls
When the stack ( flue pipe ) is cold the detector contacts should be
in the closed ( made ) position, and the contacts should be open
when the stack is hot .When you have a call for heat the thermostat
makes a circuit between the 2 "T " terminals on the primary which
will pull-in the load relay ( labeled 1 K on diagrams ). The circuit
that pulls - in the load relay includes the temperature controller (
usually a room thermostat ) the safety switch contacts , the built -
in transformer, the detectors contacts and the safety switch heater.
Before the system can begin a call for heat, the “cold contacts
“must be in the closed position which indicates “no flame present "
and the safety switch must be made .
When relay 1 K is energized, both the ignition transformer and
burner motor are powered through contact 1K1. Simultaneously through
contact 1K2 a circuit provides separate path for current to by-pass
the safety switch and detector contacts. We call this circuit the
“hold - in circuit '. At this point there are two circuits
operating.
One circuit has a portion of the transformer powering, through the
1K2 and detector contacts the safety switch heater. The second
circuit uses another portion of the transformer energizes the
thermostat , relay 1K ,safety switch contacts and relay contacts
1K2.With these 2 circuits in play when the detector senses that heat
is being produced the detector contacts opens the safety switch
heater circuit. The burner, under normal conditions, will continue
to function until the thermostat is satisfied. Should the burner
fail to light the circuit will continue to heat the safety switch
heater and after +/- 70 seconds will open its safety switch contacts
, shutting down the burner " on safety " .The burner , to be
restarted , must have the safety switch reset manually .In case of
flame failure while in the "running mode " the detector ( bi-metal )
will cool and it's contacts will close energizing the safety switch
heater and after approximately 70 seconds it will lock out on safety
which will require again manual reset.
Stack Relay Operation - RA 117 and RA817 style controls
Physically, then you can easily distinguish between the Intermittent
and Interrupted type stack relays - when you remove the covers from
each style, the intermittent type has one switching relay and the
interrupted style uses two relays in its circuitry. In both the RA
117 and the RA 817 the 1K relay powers the ignition transformer and
the 2K relay operates the burner. With this circuitry you can shut
down the ignition after the flame has been proven. The cold contacts
are closed when the burner is shut down and the hot contacts are
closed when the stack is hot.
Again , when we have a call for heat from the thermostat , a circuit
is made between the two " T " contacts ( also labeled - W and B )
,relay 1K ,the safety switch contacts ,the transformer , safety
switch heater and the cold contacts . When the relay 1K is energized
the ignition transformer is powered through contact 1K1. Physically
the transformer is wired to the # 4 terminal on the RA 117/817. The
second relay in the RA 117/817 is powered from the “on board
transformer “, through the safety switch contacts, contact 1K2 and
the thermostat. Relay contact 2K1 powers the burner motor which is
wired to terminal #3 (along with the oil valve - if any).The safety
switch HEATER will stay energized while the cold contacts remain
closed. This circuit uses part of the transformer, the cold
contacts, 2K2 and 1K3.
When the left side of the cold contacts opens the safety switch
heater will stop to heat. When the right side of the cold contacts
open, the ignition will be de-energized because relay 1K has dropped
out. Simultaneously, the hot contacts must be closed in order to
keep relay 2K energized. This " hold - in " circuit contains the
thermostat, safety switch contacts, the hot contacts, part of the
transformer and 2K2
On a call for heat , should the burner fail to light , the cold
contacts will remain in the closed position , the safety switch
heater will continue to heat the safety switch until after the
timing of the safety switch causes the switch to open . It must be
manually reset. Should flame failure occur during a call for heat
the stack will drop in temperature which will cause the detectors
hot contacts to open and relay 2K will drop-out which will shut down
the burner? In approximately 2 minutes the cold contacts will close
and energize the safety switch heater if there is still a call for
heat from the thermostat, both the ignition and burner will be
re-energized. You will have 70 seconds to re-establish a flame- if
you don't the unit will drop -out on safety and must be manually
reset.
Next Month in “Sales Bytes "-- All about Optical Sensor Oil Burner
Primaries
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Questions from the field - August 2006
edition
OIL BURNER FLAME SENSING SAFETY
SYSTEMS
Last month's article dealt with older style, thermal sensing
technology used in oil burner flame safety systems. This month we
will discuss the two piece oil burner flame sensing safety systems,
with the focus on the sensor.
Current technology allows us to use detectors that are faster to
respond to the combustion process through the use of solid state
electronic components, rather than the bi-metal type censors that
have been used, and continue to be used so successfully today. Next
month we will cover the relay / safety switch portion of this two
piece system.
Two piece oil burner systems first were introduced to OEM's in 1960
- these initial systems still used sensing devices that relied upon
changes in temperature to operate the oil burner. Remotely mounted
relays continued to be used to switch the load of the ignition
transformer, burner motor and safety switch. Generally, these relays
were mounted on oil burner housing. An evolution of types of sensors
occurred with Honeywell and General Controls (then the Ray Brothers
- later to become General Controls) leading the industry. General
brought to market a thermal sensor that mounted on the fuel line,
just behind the oil nozzle. It was wired to the remotely mounted
relay with a 3 wire lead . Honeywell countered with 3 different
sensors (all thermally activated) and the manufacturer could choose
the type that best suited his requirements - each was wired to the
relay with a 2 wire cable. Many of the systems that used the
Honeywell stack mounted, remote sensors (C550), are still in service
today and replacement C550's are still available. The other sensors
Honeywell supplied were the C552 - a thermal sensor that mounted in
the burner tube, and the C551 - a thermal sensor that utilized a
thin sensing rod that was inserted into the combustion chamber. For
several years, the relay portions of the systems were modified, but
the sensors remained virtually unchanged.
Current Systems
In 1964, Honeywell introduced an oil flame detector, for residential
size burners, that uses solid state technology. This new detector
consists of a photocell, cell holder, mounting bracket and a 2 wire
wiring harness. The photo cell responds to light, not temperature as
did the previous sensors. The sensitivity to light is provided
through the use of a chemical called Cadmium Sulfide.
The Cadmium Sulfide's (CS) electrical resistance changes as light
intensity changes (and almost instantaneously) When there is no
light present on the face of the cell , the electrical resistance
through the CS is extremely high , on the magnitude of over 400,000
Ohms and at that, point serves as an electrical insulator. When
light intensity increases, the electrical resistance decreases. When
there is sufficient light present the CS will allow current to flow.
This ability will allow an electrical circuit to be completed
through the CS when a flame is detected in the oil burner/combustion
chamber. As light intensity increases, just slightly, the resistance
decreases, however, the amount of light reaching the cell must
reduce the cells resistance to its normal operating - which is
normally less than 300 Ohms to !000 Ohms in normally adjusted
burners -in burners that are in need of service , CS cell resistance
can go well over the maximum of 1600 Ohms . At this point, the 1600
Ohms (or above) will cause the relay to trip out on safety. If, when
you measure the resistance with an Ohm meter and high resistance is
present , you will want to check for a dirty lens on the cell , the
cell may have lost its vacuum or the burner may need adjusted (air
ratio, oil pressure etc.). These CS cells will respond to any light
in the visible spectrum, including artificial light, from such
things as flashlights, electric lights and daylight .Most of the
light from gas burners is not in the visible range and therefore,
they are used, only very infrequently in gas burning equipment. When
CS cells are used on gas burners, the cell needs to be applied so
that it sees a fuel rich portion of the flame where complete
combustion has yet to occur.
Cad Cell Construction
Close examination of a cad cell (White Rogers also uses CS cells
with some of their systems) reveals it is made of a ceramic disc
that is coated with cadmium sulfide over which a conductive grid is
placed. Two electrodes are attached to the ceramic disc which will
carry an electrical signal to the primary relay. When the cell is
manufactured, it is enclosed in a glass- to-metal seal from which
the air is evacuated. This prevents the CS from deteriorating.
Cad Cell Mounting
Most oil burners that use CS detectors have the cell mounted
directly behind the static disc, so that it may view the flame
through an opening in that disc. This positioning allows the cell to
be protected from the oil spray and products of combustion. In
addition the cell face should not be exposed to high ambient
temperatures - short term 140 F or 120 F normal operating
situations. Some burners have the detector mounted in the rear of
the burner, above the combustion blower wheel. In any event, the
normal operating range for CS resistance should be 1000 Ohms or
less. The cells resistance wills, under normal conditions, increase
gradually as dirt, soot and oil/grease accumulate under standard
operating conditions. You should never have any reason to change the
original mounting location. This is the factory approved location
and was accepted for proper operation from that location .The cell
may be removed from the receptacle for cleaning. Honeywell CS cells
can be replaced, if needed, - however, do not replace a White-
Rogers cell with a Honeywell cell or vice versa. You need not
purchase a C554 (replacement cell, socket, bracket and wiring
harness) for service - just purchase for Honeywell replacements the
# 120367.
Next Month
We will review the different relays that work with Honeywell CS
cells Watch for these topics in future issues - Hydronic Zone Valves
- Switching Relays and Hydronic Relays.
Do you want some information on a particular controls problem?
Bill can be reached at 281-537-2701 or
threesons@ev1.net

Oil Burner Safety Switch Circuits -
September 2006
Part 2 of 3
In previous issues of “Sales Bytes" we discussed the operating
sequences of both Thermal Sensitive oil burner primaries and Optical
flame oil burner flame sensing systems (Cad Cell Primaries). This
month we will review some of the details about the different types
of safety switches used by Honeywell in their oil burner primaries
.The evolution of these switches has been nothing short of amazing
(but seemingly agonizingly slow). I suggest that if you are deeply
involved with oil burner primaries that you would be well advised to
contact Honeywell's web site for specific copies of the
specification sheets in which you are in need of information - there
is no charge - they are extremely detailed in every facet of the
devices' installation, servicing and troubleshooting . You may
contact Honeywell @
http://customer.honeywell.com or by
telephone to their technical “Hot Line “@ 1-800-468-1502. Please be
specific about the device in which you are interested.
The purpose of the " Safety switch " is to shut the burner down in
case of a malfunction in the burners operation There have been
approximately 4 different types of safety switches ( plus many
iterations ) which have been used since the advent of the "Stack
Switch".
The first Stack Relays used an open type of switch concealed under
the cover - an electrical / mechanical type switch that, as the
bi-metal heated during a burner malfunction, would warp the bi-metal
switch open - thus shutting down the burners operation.
Since the safety switch was exposed when the primary’s cover was
removed the stories are legend about clever homeowners use of rubber
bands , matchbook covers , dental floss and various other materials
to by-pass the safety switches' purpose - No need to cover them in
detail here - hopefully most of these stack relays are out of
service now , or at least they should have been replaced by this
time .These models would include the R116 and R117 - ( Not the more
current RA116 and RA117 units ). Most stack relays used safety
switch timings of approximately 70 seconds .
Cad Cell Primaries - (1961---) two principle types of safety
switches have been applied to these systems and they are easily
identified. On the earliest versions (R8118, R8169 and similar line
voltage primaries) an electro - mechanical design was incorporated
into these type devices to respond to a loss of flame in the burner
system and to stop the burner from continuing to operate.
Electronics allowed Honeywell to introduce, in the "Cad Cell "
primaries, a much closer control of safety switch timings because
ambient temperatures and wide swings in voltage could more easily be
handled...
Honeywell, with the introduction of these new cad cell primaries,
was now able to offer to OEM's a choice of safety switch timings -
15, 30, or 45 seconds. The OEM chose the timing which matched the
capacity of his burner - up to 4 GPH. MOST RESIDENTIAL BURNERS USE
THE 45 SECOND TIMING, WHICH IS THE VERSION CARRIED ON DISTRIBUTOR'S
SHELVES FOR REPLACEMENT WORK. THE ADMONITION IS, NEVER USE A SAFETY
SWITCH TIMING LONGER THAN ON THE RELAY SUPPLIED BY THE BURNER
MANUFACTURER. The problem is obvious and does not need further
discussion.
In each event, when the relay “locks out ", the safety switch reset
button must be manually be reset. The burner will remain disabled
until the red reset button is pushed. The resetting of the reset
button will allow the burner to restart as long as there continues
to be a call for heat.
The earliest cad cell relays made by Honeywell utilized a relay
called a "sensitive relay" which was incorporated into the safety
switch circuit. The relay used two bi-furcated contacts (DPDT) in
the safety switch circuit to be able to switch the extremely small
currents that are carried through the cadmium supplied cell. These
contacts were described as “whisker” contacts and their very small
surface area prevented an accumulation of dust occurring which could
cause nuisance shutdowns. These relays were easily identified
through these clear plastic cover around the relay. No replacement
or service is possible on this relay If the unit has failed you must
replace the entire relay. Later versions of the cad cell oil burner
primary(R 8184 G etc...)Use a solid state equivalent for the safety
switch circuit .The Triac, bi-lateral switch, 2 resistors and 2
capacitors make up the components that replace the older
electro-mechanical version of the safety switch circuit.
The solid state flame sensing circuit is designed so that the Triac
will conduct current only when the resistance is high (indicating a
lack of an adequate burner flame). When the cad cell resistance is
high , the voltage across the bi-lateral switch exceeds the break
over voltage which causes it conduct current and thus triggers the
Triac . The capacitors purpose is to supply pulse of current on
every 1/2 Hertz in order to assure that the break over voltage is
exceeded .When the Triac is in the conducting mode (when the cad
cells' resistance is high) when you have a call for heat from the
system's thermostat the # 1 K relay (Shown in the Honeywell
diagrams) gets energized. When Relay # 1K is energized it will close
its contacts # 1K1 and 1K2 and the burners ' components (Burner
motor, oil valve and ignition transformer) are energized .When the
flame is established, the cad cells' resistance will reduce, the
voltage across the bi-lateral switch falls below the break over
voltage point which causes the Triac to stop. Then the Triac switch
stops conducting, which causes the safety switch to drop out of the
circuit allowing the oil burner to continue to run. The # 1k relay
stays powered through its # 1K1 contact and will continue UN till a
loss of flame or the thermostat is satisfied.
On flame failure, the cad cells' resistance increases until the
Triac is energized. At this point the safety switch heater continues
to heat till the bi-metal warps enough to break the its circuit
which then causes the burner to shut down. The red reset button must
be manually pressed for the burner to be able to restart.
Next month we’ll take a look at today’s current models of cad cell
primary controls.

Oil Burner Safety Switch Circuits -
October 2006
Part 3 of 3
In previous
issues of “Sales Bytes" we discussed the operating sequences of both
Thermal Sensitive oil burner primaries and Optical flame oil burner
flame sensing systems (Cad Cell Primaries). This month we will
review some of the details about the different types of safety
switches used by Honeywell in their oil burner primaries .The
evolution of these switches has been nothing short of amazing (but
seemingly agonizingly slow). I suggest that if you are involved with
oil burner primaries that you would be well advised to contact
Honeywell's web site for specific copies of the specification sheets
in which you are in need of information - there is no charge - they
are extremely detailed in every facet of the devices' installation,
servicing and troubleshooting . You may contact Honeywell @
http://customer.honeywell.com or by telephone to their
technical “Hot Line “@ 1-800-468-1502. Please be specific about the
device in which you are interested.
Current Cad Cell Primaries --- (R 7184 Family)
In recently introduced cad cell primaries, the miniaturization of
electronic components has allowed Honeywell to incorporate a number
of new features which enhance the controls' versatility and
desirability to the manufacturer, service technician and homeowner.
This new family of cad cell oil burner relays use a status LED and a
new type reset button which, when used together, will provide an
indication of the following :
# 1. - Presence of burner flame
# 2. - Relative flame level (Cad Cell Ohm Resistance)
# 3. - The control is in lockout.
# 4. - The control is in re-cycle.
This multi-function light is used together with a new style reset
button to provide the service technician with information about the
burner’s operation. These devices provide more precise control under
a much more variable range of voltages and ambient temperatures than
older style devices .The addition of various timing functions also
provides a wider range of application flexibility for OEM's These
include :
# 1. - Fuel oil valve on-timing -- 0 or 15 seconds.
# 2. - Burner - off delay timing 0, 2, 4, 6 minutes
# 3. - Lockout timing - 15, 30, 45 seconds
# 4. - Ignition carryover - 10 seconds
# 5. - Recycle delay - 60 seconds
If you have any questions that these articles haven’t answered
please feel free to contact me at
threesons1@peoplepc.com.

Residential
Hydronic Zone Valves -
December 2006
Facts About Application, Selection, Sizing and Servicing
• Capacity Index (Cv) defines just how much water can pass through a
valve at a specific pressure drop (PSI). The OEM's spec sheets
provide graphs of these capacities.
Example : A valve with a Cv rating of 7 means that with a pressure
drop of 1 PSI across the valve that the valve can handle 7 gallons
of water per minute (GPM). A valve rated at 2 Cv will carry 2 GPM
with a pressure drop of 1 pound across the valve. Cv ratings are
universally used throughout the industry.
• Changing the inlet and / or the outlet size of the valve does not
necessarily alter the valves capacity (flow rate). The valves
internal porting governs the flow rate.
Example: Honeywell's V8043A1003 1/2" x 1/2' valve has the same
capacity as their V8043A1029 3/4x 3/4”. The valves capacity is 3.5
gallons per minute with a 1 pound drop across the valve. With
different pressure drops across the valve, the capacity changes. For
example, with a pressure drop of 5 PSI, the valves capacity (
V8043A1003 ) becomes 8 GPM. The same valve, with a pressure drop
across the valve of 1/2 PSI, the capacity changes to 2 ½ GPM. For
most residential systems a valve with a 3.5 Cv rating will suffice
for the average zone. This would provide approximately 35,000 BTU's
at normal operating temperatures .Valves are available in 1, 2.5,
3.5, 4, 7 and 8 Cv ratings.
• Certain manufacturers have different valves for different media,
i.e... One valve for hot water, another for cold water and still a
different valve for steam systems. Honeywell is a typical in
providing this choice.
• If you are providing or servicing a low voltage zone valve system,
I would caution you in selecting the step-down transformer you
supply to power the system’s components. In order to determine the
proper size transformer ( Va rating ) that should be used - multiply
the valve's power need (coil draw of the valve motor, i.e.. .32 amps
AC .etc . ) x 24 volts AC . That provides the amount of energy
needed to power 1 zone valve.
Example - .768 Volts x amps. Multiply the number of zone valves to
be used in the system for the total VA required (for the zone valves
only). If you will have 8 valves in the system, you will require 61
+ VA In this example the best (least expensive route) would be 240
VA transformers or a 40 and 30. A 49 VA and a 20 VA won't hack it.
Prepare for the worst case scenario: Don't overload the
transformer's total output - When power failure occurs, all valves
will try to open simultaneously - the valve motors inrush needs will
cause the transformer to fail.
• Many valves have manual openers (some are at extra cost). When
used during a power failure, these openers will return to the
normally closed position, ready for the next power failure. Be
certain to brief the home owner on this feature. This won't provide
a lot of comfort, but it probably will keep some degree of
livability in the home through the effects of gravity.
• Most complaints of “water hammer” are a result of valves being
installed in the piping backwards - yes, backwards.
• Using a valve with an "end switch" (optional feature on some brand
valves) will allow you to power a circulating pump (up to 4.4 amps @
120 Volts) without using a relay. Take care to check pump's current
draw.
• Honeywell valves (V8043 type) should be used only in systems that
do not contain Dissolved Oxygen. Most frequently systems that use
constant resupply of make-up water will contain “Dissolved Oxygen”.

Mr. Control Pro Most
Frequent Questions for 2006
January
2007 issue
In this months' issue of " Sales Bytes " I'll try to catch up with a
number of questions I've received from a number of people about the
same ( or similar ) subjects.
1. 24 VAC pilot igniter on Honeywell’s
“Smart Valve " system.
• The normal warm-up timing for the 24 VAC igniter is 2 +/- seconds.
This timing will lengthen - slightly - as the igniter ages.
• The warm-up timing for the 120 V ac igniters varies - depending on
the model - either 17 seconds or 34 seconds. Some new models, used
with advanced versions of the “Smart Valve “systems can have warmed
- up timings as short as 5 seconds.
• The line voltage igniters (normally Norton is the largest supplier
of these items) are made of Silicone Carbide alloys and this
material has a very high initial resistance to current flow - thus
the long warm-up timings.
• The 24 VAC igniter is constructed from an alloy of Silicone
Nitride, is much less brittle than Silicone Carbide and has a very
low initial resistance to current flow. Therefore it reaches the
proper temperature for gas ignition very quickly .
2. New gun-tube type oil burners will normally provide a very low
initial Ohm reading from the Cadmium cell on start up (generally in
the range of 100 to 200 Ohm’s. As the burner fires, through time,
the blast tube will accumulate oil and soot, thereby providing a
condition for adsorption of light which is needed for flame
detection on the “Cad Cells " face. This reduction of cell light
causes an increase in Ohms resistance in the Cad cell. When this
resistance reaches a level of over > 1000 Ohms the cell will need
cleaning or even replacing. The oil burner primary responds to
differing signals from the “Cad cell " to either permit the burner
to operate or shut down on “safety "
3. The load switching ratings for relays and for contactors are
those ratings based upon those certified when they are tested in the
vertical mounting poison. Those ratings will normally decrease when
the relay or contactor is mounted horizontally. This really applies
only to non-electronically constituted devices. “The older stuff -
open contacts etc... - "
4. “Smart Valve” igniters should measure about 3.7 + /- Ohms when
new, cold -not powered. As the igniter ages its' resistance will
increase. When its cold, measured resistance increases to 10 Ohms it
must be replaced. Constant, reliable operation depends on the
quality of the igniter. Hot spots on the igniter signal the need for
replacement.
5. When the manual opener is used on Honeywell's V8043 family of
hydronic zone valves ( because of a loss of power ) the valve will
automatically cycle to the closed - normal operating position when
power is restored. You achieve only about 60% of full flow in manual
operating position.
6. Honeywell builds V8043 zone valves specifically for steam
service. Don't attempt to use their regular V8043's on steam. The
revolving valve ball will not survive steam temperatures.
7. The Honeywell V8044 water service valves are DIVERTING VALVES AND
ARE NOT INTENDED FOR USE AS MIXING VALVES.
Hopefully these comments will answer some of the things that have
raised questions for either yourselves or your technicians.

Thermocouples and Self
Generators February
2007 issue
While I haven't directly addressed the
issue of Thermocouples and / or Self-Generating "D. C.” power
supplies, I continue to receive questions about these devices. That
tells me there must be some misconception and misunderstanding about
these devices which makes this topic quite timely. I'll cover single
thermocouples Operating Principles this month and continue next
month with Operating Standards by code bodies.
The fundamental operating principles of thermocouples have been used
in the HVAC industry since about the 1910's. Through the years these
devices have been used in both heating AND cooling systems (Gas
Fired A/C units). Not counting the millions of gas fired water
heaters, it is estimated that there are over 40 million gas fired
heating appliances in service today. Furnaces, boilers, unit
heaters, spas, duct heaters, wall heaters and floor furnaces, just
to name a few. So we need a fundamental understanding about these
units. How they operate, how they are tested and serviced.
OPERATING PRINCIPLES
Two dissimilar metals are bonded together at one end (usually
stainless steel and Copel - a copper/nickel alloy - for the
temperatures seen in heating / cooling systems). Other applications
for this technology, i.e., industrial temperature reading etc.,
utilize other types of metals joined together - but they each
operate exactly the same way. When the welded junction of the two
metals is heated (called the hot junction) the heat applied will
create an energy flow. For or our purposes we will work with current
in the magnitude of +/- 30 millivolts dc. This amount of current
will be sufficient to energize the coil of the pilot gas valve and
will normally hold the valve seat in the open position. Important:
the energy created by heating the hot junction of the thermocouple
is not sufficient, in and of itself, to pull the valve seat up
(open). First, you must turn the pilot gas cock knob to the pilot
gas flow position and depress the knob - this action will force open
the pilot gas valve seat ,sealing it against the pole pieces of the
"horseshoe" shaped magnet. The magnet is not strong enough to
"Pull-in" the valve disc - just strong enough to "Hold it in".
Having held the gas cock in the depressed mode for + / - one minute,
manually igniting the pilot gas, the current generated by a properly
sized and adjusted pilot, heating a properly located and shielded
thermocouple should hold the pilot gas valve open. Once the pilot
valve is held in the open position, by the current generated by the
thermocouple, you must then release the pilot gas cock - the pilot
gas should continue to burn and you must turn the gas cock to the
"on" position. With a call for heat, the main valve should open and
the main burner should safely light off. On a loss of the pilot gas
flame, (for whatever reason - drafts, gas pressure issues, clogged
pilot orifices etc...) the thermocouple tip will cool below the
temperature required to heat it sufficiently to generate enough
current to hold the pilot gas valve open, and should this event
occur, the main fuel valve will be starved of gas -even though the
main valve could remain open due to a continuing call for heat from
the controller (usually a thermostat) Thus, the burner would safely
shut down. The safety built into the operating system of the
appliance depends upon a correctly functioning thermocouple / pilot
burner combination.
Next month: Operating Standards

Thermocouples and Self
Generators March
2007 issue
# 1. - Standards for gas burning
appliances are written by "ANSI" - the American National Standards
Institute. The appliances are tested for compliance to these
standards by approval bodies, of which there are several - A.G.A.
(America can Gas Association) being the most widely recognized.
These bodies DO NOT write the standards to which they test.
The standard fitting for thermocouples operation is the standard
that says, "The safety shut down system must recognize the lack of
pilot flame (flame failure) for gas burning appliances, of less than
400,000 BTUH capacity, in 180 seconds or less and shut the system
down.” THAT'S 3 MINUTES. Most thermocouples will cool down
sufficiently, to shut the system down, in about 60 seconds - but 180
seconds will meet code requirements. Modern “Flame rectification”
systems react in + / - 2 seconds - a whopping difference. However,
thermocouple operated appliances are still a very safe operating
system indeed.
# 2. - With no load connected to the coil, a new thermocouple will
usually be capable of producing an output of +/- 30 millivolts. This
output is based on a tip temperature of approximately 780 -800
degrees F. As you increase the tip temperature the millivoltage
output will increase and when heating the tip with propane torch you
could easily find an output of over 40 millivolts. However the
cooler you are able to run the tip temperatures (less than 1000
degrees F is optimum) the longer life expectancy for the ‘couple.
Many manufacturers will not warranty their thermocouples - Honeywell
warrants all of their equipment- including 'couples. They have two
quality thermocouple devices available - the Q340 - rated as a 10
year life average and the Q390 which is a 5 year device.
In order to create the current flow required a temperature
differential must be achieved - the greater the dif-Terence between
the hot junction and the cold junction -the greater the millivolts
output. The maximum temperature on the cold junction allowable is
780 F. Maximum hot junction is 1400 F The ideal temperature on the
hot junction is 780 -800 degrees F. This, for example, should be the
range you would reach with a pilot, such as Honeywell’s Q314 using a
.018 natural gas orifice and pilot gas with a pressure of 3.5
"o.k.”. These factors should produce an optimum operating situation
for a thermocouple.
The Q340, 24 inch length, has a resistance of 0.02 Ohms, its lowest
acceptable open circuit output is 18 millivolts and under. Turndown,
open circuit is minimum 2 millivolts. If you require further
explanation of this data, feel free to call me. The lowest
permissible open circuit rating is based upon the lowest acceptable
turndown rating of 18 millivolts.
I'll continue this discussion of “Thermocouples, Thermopiles and
Pilots in next month’s issue.

When is a Contactor
Not a Relay? June
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
It’s cooling season, and you’ll be
replacing contactors and relays every day. Aren’t all contactors and
relays pretty much the same? Nope. As you might expect, there are
many differences. This month I’ll write about the basic
characteristics of contactors, and next month will be the same on
relays.
U. L. says anything over 20 amps full load (AFL) or more is a
contactor. They are three types:
1.
General Purpose contactors
2. Definite Purpose contactors
3. Motor Starters
All these switching devices share many
features in common. Each on has one or more sets of contacts that
will open or close a controlled circuit. Each is activated by a
separate controlling circuit. For example, a 24 VAC control circuit
through a thermostat might connect power to a 120 VAC blower motor.
Most contactors use a magnetic coil in the control circuit that,
when energized, will pull in the load bearing contacts. The load
contacts are generally made of silver cadmium oxide and the amount
of silver in the contacts and the method used to bond the contacts
helps to define the maximum load the contacts can carry.
Any contactor may have 1-4 sets of switching contacts, known as
“poles”. These poles may be in the normally open (NO) position when
there is no power to the controlling circuit, or they may be
normally closed (NC) when there is no power to the controlling
circuit.
General Purpose Contactors
As the name implies these contactors can be used in a wide variety
of applications. They are generally build for a longer life and can
stand repeated changes of replacement control circuit coils.
Definite Purpose Contactors
These devices are used in residential and light commercial AC
systems, heat pumps and electric furnaces. Each contact is built to
handle a specific load, i.e., 25 Amps. There is an addition rating
called “locked rotor” which is the starting current required to get
the motor off of its stopped condition into a running condition. The
locked rotor rating may be as much as 6 times the running amp
rating. Today’s motors are more efficient than those in the past and
so the locked rotor rating is of less importance than it has been.
Beware of replacing contactors on old equipment...the older the load
device the higher the starting amp requirement you will have.
Motor Starters
Motor starters are contactors that are designed to switch heavy
motor loads and may include additional features such as overload
protection, holding contacts, step resistors, disconnects, and more.
Older style compressors and some fan motors are usually controlled
through motor starters.

Relays: Everything You
Need To Know July
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
Last month’s discussion centered on
contactors. These devices are used in our industry to switch larger
electrical loads in excess of 20 amps. Generally these loads are AC
compressors and air handler motors. This month our focus will be relays.
Relays allow us to remotely control many types of circuits and loads and
also provide the ability to control larger loads with very sensitive
controller-devices that would not be able to switch these loads by
themselves.
The advent of solid state components and micro-processors makes it
virtually impossible to describe here the variety of types of switching
configurations and mounting methods to be found. Many relays are mounted
on circuit boards and they are not designed to be replaced in the field
- if the relay fails the entire device must be replaced - such as those
used on Integrated Furnace Controls and Electronic Fan Timers. A high
percentage of hydronic heating systems, for example, use remotely
mounted relays for control of the circulating pump(s) and these systems
typically utilize switching relays encased in cases and covers. Many
case and cover relays may be replaced on the job. For example, RBM and
Honeywell have manufactured, for years, field replaceable, plug-in style
relays, which are mounted on circuit board receptors (held in place by
"bails ").
Relays are called, frequently; by the name of the circuit function they
are to provide- Thermal Delay Relay, Time Delay Relay, Impedance Relay,
Sequencing Relay etc...
A description of the function provided by the Impedance relay is as
follows. An impedance relay permits (in a residential type A/C sytem)
compressor lockout and provides remote reset for the consumer. This
eliminates the necessity for a manual reset overload control or pressure
sensor. The relay has a low voltage pull-in coil and contains two sets
of contacts-one single pole/single throw- normally open (SPSTNO) set of
switching contacts and one single pole/single throw - normally closed (SPSTNC)
set of contacts. During normal operating conditions, the normally closed
set of contacts in the pressure switch and the compressor motor overload
short out the impedance relay coil. The contactor coil is wired in
series with the coil of the impedance relay . The contactor coil is also
wired in series with the SPSTNC relay contact and the overload and/or
pressure cutout contacts which are both normally closed. When the
thermostat calls for cooling, the compressor contactor is powered
through the contactor's coil, and the impedance relay's SPSTNC contacts
(which are wired in parallel with the impedance relay coil) and the
pressure switch and/or overload contacts.The high impedance of the
impedance relay coil prevents the impedance relay from pulling-in during
normal operation. Should either the pressure switch or overloads open,
the impedance relay coil is then placed in series with the contactor
coil. Most of the voltage in this circuit is used by the impedance relay
coil and as a result the compressor contactor drops out. When the
impedance relay pulls in, its normally closed set of closed contacts (SPSTNC)
opens which holds the compressor off line. While this system has lost
favor over the past few years many,many systems that use this circuit
are still in service today. To reset the circuit -simply satisfy the
thermostat and the impedance relay will drop-out. This is easily
accomplished by moving the thermostat's system selector switch to the
"off" position.
Relays that contain electro- mechanical contacts are designed to be
mounted with the mounting base in the vertical position (same applies to
most contactors). Gravity plays a role in the contact ratings and for
maximum switching service - vertical is the key word.
Another example of a relay designed with a specific purpose in mind is
the Electric Heat relay. Again these types of relays are available in a
wide variety of shapes, sizes and switching configurations- with and
without cases and covers for panel and individual mounting. Some include
step-down transformers in order to provide low volt circuit power for
thermostat control.
Sequencers designed to switch electric heat loads (baseboard resistance
elements as well as strips in central furnace systems) are designed to
carry maximum specific loads These ratings are specified in Full Load
amps, and Resistive Loads.Many also will show their rating for Locked
Rotor amps.
A typical electric heat relay is listed at U.L. with the following load
switching characteristics:
Full Load
Resistive Locked
Rotor
2.8A @ 600Vac 10A @ 600Vac
14A @ 600Vac
3.5A @ 480Vac 12.5A @ 480Vac 17.5A
@ 480Vac
7.0A @ 120Vac 25A @ 120Vac
35A @ 120Vac
208 ,240 &
208,240 & 208,240 &
277Vac
277Vac
277Vac
It would, as you can understand, be nearly
impossible to detail all of the various types of relays available in the
market place in the space and time allotted here-manufacturers, however,
generally speaking, are quite helpful with their catalog listings. Be
carefull to select a relay that is rated to swich the load or circuit
with which you are dealing . Don't try to swich a Powerpile load with a
switch that is not specifically rated to switch “Pilot Duty" loads. The
types of devices that will satisfactorily switch Powerpile loads
normally include gold flashed contacts ( very low resistance to current
flow). Should you, by mistake, try to switch a heavier load than
Powerpile on these contacts the gold flashing will be "blown away" and
the contact will no longer be suitable for "Pilot Duty" service
See you next month with the answers to some frequently asked questions.

Transformer,
Thermocouple and Relay Tech Tips
August
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
This month I’ll answer three of the
questions I received by email in the past month:
1. What are NEMA transformers?
2. What does “open circuit” on a thermocouple mean?
3. What does “pilot duty” relay mean?
NEMA Transformers
Several have asked about "NEMA" transformers. Why it is important to
use them and what's difference between a "regular" transformer and a
NEMA transformer?
NEMA (National Electrical Manufacturers Association) has developed very
precise criteria by which the performance of low voltage (< 30 Volts
A/C) transformers is judged. It is critical, especially with the
electronic components and circuitry used in HVAC equipment currently
produced, that the equipment's system transformer produce predictably,
repeatedly and reliably voltages within a certain output range. System
performance depends upon this accurate output. The standards, to which a
transformer must perform, to be rated as a "NEMA" rated device: NEMA
Standard 20-92
With 0 % load connected to the secondary, 26 1/2 Vac-is normal, with a
range allowable of +/- 1/2 Vac output. (26 to 27 Vac is the standard.)
With 100% load (i.e... a 40 VA load on a transformer rated for 40 VA max
capacity) the secondary voltage output must be 24 Vac- +/- 1Vac. (23 to
25 Vac is the allowable output range)
With 200% load (i.e... an 80 VA load on a transformer rated for 40 VA
max capacity) secondary voltage output of 21 1/2 Vac +/- 1 1/2 Vac (20
to 23 Vac is the acceptable output range.).
Many equipment manufacturers are specifying that the transformers they
utilize on their equipment must be NEMA rated and warranties are voided
if transformers used in servicing this equipment are used.
Many different problems have been created, through the years, by poorly
performing transformers. One of the most familiar problems is when there
is "over cooling” when using the Honeywell T87/Q539 thermostat /sub-base
combination and a substandard transformer. Since the cooling
"anticipator” is the only load on the transformer secondary when there
is no call for cooling and there is a higher output on the transformer
secondary, 28, 29, 30 Vac or even higher, the 3000 ohm (+/- 5%)
thermostat cooling anticipator will overheat causing the stat to call
for cooling more quickly than needed and will remain calling for cooling
on longer than needed resulting in "over cooling" the space. Wide
temperature swings then cause familiar consumer complaints. Replace the
transformer and fix the problem!
Thermocouple Open Circuit Question
Your article about "Thermocouples" mentioned the "open circuit” range
of millivoltage outputs for "normal" single thermocouples - what should
the minimum output be with the pilot safety coil under power?
If you are measuring the "closed circuit" output of a thermocouple (each
different thermocouple will have its own output curve) the test should
be run with the thermocouple operating in its own pilot burner, with
normal gas pressure on the pilot. In other words the test should be run
with the test conditions the same as the thermocouple would operate
under normally. I can tell you that the range of outputs for the
Honeywell Q340 varies from a lowest acceptable output of 18 ma (open
circuit) with a "turndown minimum output of 2 ma, a normal open circuit
output of 26 to 32 ma and an open circuit output with a "closed circuit"
output of 7 to 9 ma.
In the case of the Q340 thermocouple and the pilot applied to the unit
must be able to satisfactorily light the main burner in 4 seconds or
less (with no singeing of a tissue placed over the vestibule opening or
"oil canning" of the cabinet) with the pilot / thermocouple combination
producing an output of 2 ma. If this test is not passed, the entire
piece of equipment under test will not pass and the OEM must go back to
the drawing boards until they can satisfactorily pass the test.
What Are Pilot Duty Contacts?
What do you mean by the term "Pilot Duty Contacts" when talking about
relays?
The term "Pilot Duty” rated contacts, when used in reference to control
devices , such as relays and other pieces of electrical load switching
equipment, refers to that specific device’s ability to switch or control
very small electrical loads (i.e.0.25 amps @ 0.25 to 12 Vdc or less )
These devices, when designed to switch these very small loads are
generally made with gold (or other precious metal ) plated or "flashed"
contacts because these precious metals have extremely small resistance
to current flow. Normally the plating is quite light or "thin' and
should you place a higher voltage (Load) on these specific contacts, the
contact will no longer be able to switch this very small electrical load
because the plating will have then been " blown" off the contacts and
will not operate satisfactorily in a millivoltage type load .
I enjoy hearing from you and trying to respond to your questions. More
answers next month.

Setting Heat
Anticipators on Electric and Electronic Thermostats
September
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
DEALER QUESTION - We are somewhat
confused about the proper way of setting heat anticipators on both
electric and electronic thermostats. I guess we don't really understand
what they are for. Further, what effect they have on the furnace's
cycling rate. Will you help us out?
ANSWER - First -the question about
the "heat anticipator purpose. The heat anticipator is an integral and
most important component in the thermostat. Without an anticipator, the
thermostat would have to rely only on its sensing element (usually a
bimetal) to respond to changes in the controlled spaces’ temperature.
These "stats" need a boost to be able to more nearly track the room's
temperature. The anticipator applies additional heat (produced by the
current flow through the anticipator) and as a result the "stats"
sensing element responds much more rapidly to room temperature changes.
An electro-mechanical thermostat, without an anticipator, is about the
same as having an automobile with square tires. The car will get you
where you are going but neither very rapidly or smoothly- the same may
be said of an anticipator-less thermostat.
There are two types of anticipators used in electro-mechanical
thermostats today:
#1 - Fixed (non-adjustable). Thermostats that employ fixed
heaters are designed to match the needs of specific "loads". For
example- a special model is designed specifically to operate " Powerpile
" type gas valves. These thermostats have a fixed (non-adjustable ) heat
anticipator and they will not work effectively with any other type of
load. Sometimes they are referred to as “Pilot Duty " rated thermostats.
In most instances they are able to carry only loads of 750 millivolts or
less.
#2 - Adjustable heat anticipators. Adjustable heater thermostats
are found on well over 99% of equipment systems in use today. As the
name implies - the "heater" is adjustable and may be adjusted to match
many different "loads" Negates the need to have a special thermostat for
every load. What a nightmare that would be. We describe the "heater" as
"wire wound" And it has a scale plate connected - the scale plate is
graduated in tenths of one amp. The Honeywell T87 has a scale plate (On
the standard model) from 1.2 to .1 amps. The adjustment pointer may be
moved to any point along the scale. And should be set on the proper amp
draw marking that will create the “Cycle " pattern needed for that
particular piece of equipment Later we will cover the "Cycle" rate
issue.
#3 - Fixed “Carbon Heaters". The earliest thermostats with heat
anticipation are no longer built (such as the Honeywell T11, T147, T19,
T109, T111and TM147). They used small carbon, color coded, fixed
resistance plug-in style heaters. These heaters were available in about
19/20 resistances. The technician had to pick-out and plug-in the
resister that most nearly matched the load he wished to cycle There are
still, even today , some of these thermostats in service -should you
come across one of them - for your customers sake please replace it.(
and put it in your showroom museum of old controls etc,)
Electronic thermostat heater setting will be covered later in this same
article
The second part of his question dealt with
"cycle rate". The proper "Cycle" rate is determined (through exhaustive
laboratory testing and analysis) by the equipment manufacturer and with
a very few exceptions will follow the guidelines shown below. You should
however, follow the recommendations of the equipment manufacturer when
they are available to you. By definition a CPH is one full "ON" and one
full "OFF" period on the appliance. Cycle rate settings are based upon
the load on the equipment @ 50%. For example : a 6 cycle rate would at
50% load produce a timing of approximately 5 minutes "on" and 5 minutes
“off" at design.
#1 - Use 1 (one) Cycle per Hour (CPH) for
one and two pipe steam systems
#2 - Use 3 (three) CPH for Conventional hydronic systems. (non-fin tube
type radiation)
Condensing style gas furnaces #3 - Use 6 (six) CPH for Conventional
style fossil fuel furnaces (Gas and Oil)
Hydronic Systems using zone valves (copper and aluminum fin tube
radiation) matching the anticipator to the zone valves current draw.
#4 - Use 9 (nine) CPH for ducted electric resistance furnaces. It is of
critical importance that the thermostat heater be set properly in order
to achieve the optimum operating efficiency and to provide the maximum
comfort possible for the customer.
The details that have dictated these cycle patterns are far too complex
to cover in any detail in the space we have available here but, rest
assured-these have stood the test of time. Factored in , among many ,
many considerations are such things as the design of the heat exchanger,
its adsorption and desorption rates etc.The technician's ability to
install and set-up the thermostat correctly is of paramount importance
and only when the correct procedures are followed will the user receive
all the benefits for which he has paid.
In order to set the heat anticipator to
match the CPH rates shown above- use the following chart. Please, first
measure the circuit's current draw at the thermostat- not at the
equipment. This amp reading will be the value you must use to determine
the proper set point on the scale for the cycle rate you want to use.
#1 - 1 (ONE) CPH Multiply your amp reading
X TWO. For example - if you read .45 at the thermostat (system "on” for
at least one minute before reading) multiply the .45 by two - or .9.
That is the proper place to set the pointer.
#2 - 3 (THREE) CPH Multiply your amp reading X1.4 ( 140%)
#3 - 6 (SIX) CPH Use the amp draw you get at the thermostat for the
anticipator set point For example -read .8 Set the pointer at .8
#4 - 9 (NINE) CPH. Multiply your thermostat reading X .7 (70%) Example -
you read .54amps. Multiply .54by 70% or .378 set the pointer at about
the .38 to .4 spot on the scale.
ELECTRONIC THERMOSTAT CYCLE SETTING
There are many, many different brand
electronic thermostats available on the market today. Obviously on have
chosen Honeywell for illustration purposes.
When the installer elects to install a Honeywell Vision PRO" he merely
needs to wire the terminals that are required to operate the system and
mount the "stat". No more does he have to make meter readings to set the
anticipator.
Following the specification sheet he needs to enter "The Installer
Set-up Mode". When the "Vision Pro's" backlit screen is pressed it will
light up a reveal a matrix. He then selects the cycle he wishes to use -
press that option and the cycle rate selection is completed. I suggest
that the "tech" first read over the instructions so that the many
options in this family of thermostats makes them indeed "Universal” in
their wide range of applications.

Charcoal Filters
and Redundant Gas Valves
October
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
Several questions have come in (by phone
and e-mail) since last month's edition of "Sales Bytes" and some of them
may strike a familiar chord with some of you, as well.
Question # 1.
How much "Ozone" (O/3) will charcoal filters adsorb? We use them in some
electronic air cleaner applications and they seem quite effective as
many of our frequent "Ozone" complaints have been greatly reduced?
Answer # 1.
Charcoal, which is made from activated carbon , does not really adsorb
"Ozone" , but in fact, the " charcoal " acts as a catalyst for two O-3 (
unstable oxygen ) and it re-arranges it's molecular structure to three
O-2 , normal oxygen.
"Charcoal" will, however, adsorb other gases ( Cooking, smoking pet
odors etc...) but it is not designed to remove particulate matter-
although if left unprotected by an effective air filter it will in fact
load up with lint, dust ,dirt etc. very quickly and consequently need
"cleaning" or replacement fairly quickly. When the activated carbon has
loaded to its capacity it will then desorb the sum of the gases it has
removed. Sometimes the outgassing is worse than any of the individual
odors alone
High pressure drop is a large problem when dealing with "charcoal
filters" It's been demonstrated that 1/2 " thick "egg crate" style
filter which is coated with activated carbon works best in regular HVAC
systems because of it's low Delta-P.
Question # 2.
We have a number of heating units that we service that have
non-redundant gas valves and that utilize an additional limit that is
generally located in the combustion chamber. We consistently have
"call-backs" on these jobs because, I believe, we have replaced either
the limit or thermocouple in error. Got any suggestion?
Answer # 2.
A little history, which may help to explain some of the questions you
have When ANSI changed the gas train requirements as of Jan. 1st , 1979,
they wrote a requirement that said all new equipment must be structured
so that they met one of these three dictums.
# 1. The gas train must include a redundant (dual safety shut-off) gas
valve -or,
# 2. The gas train must have two (2) single safety shut -off valves,
piped in series and wired in parallel -or
# 3. The control string in the system had to have an additional high
limit, wired in series, with the rest of the required limits. In
addition, this limit had to be a "one - shot" limit. This limit would
have to be in addition to any other limit normally required in an
appliance of its type.
I mention this requirement because the extra limit, usually similar in
design (snap-disc variety) to limits used in electric resistance
furnaces, was wired into the thermocouple circuit. When the extra limit
would open, it opened the circuit to the safety shut-off coil which in
turn closes the main shut - off valve. Thus achieving, to some degree,
redundancy.
The critical point to remember is that if AWG 18 wire is used to wire
from the limit to the thermocouple circuit a maximum length of 13 inches
of wire be used - and the thermocouple has to be a maximum of 18 inches
in length. When the wire between the thermocouple and the limit is AWG
16, the length of wire should not exceed 22 inches and the thermocouple
should not be longer than 18 inches in length. Should the connecting
wire from the limit to the thermocouple be AWG 14, the wire length can
be 35 inches and the thermocouple 18 inches long.
Various models of thermocouples will have slightly different wire length
requirements (mostly more limiting). I have quoted the data for
Honeywell's Q 340 thermocouple series. The important point to remember
is ”Never use a longer replacement thermocouple than the original
thermocouple used in the equipment”. The added resistance can and will
cause nuisance problems.
Question # 3.
With electric thermostats (mercury switch type) where is the best place
to take amp draw readings in order to set the heater correctly? Most of
the men I work with tell me to take the readings at the valve- it will
save a trip up the stairs. What do you recommend?
Answer # 3.
Phillip, I ALWAYS advise, when asked, that these readings be made at the
thermostat -across the R and W terminals (stat off of the sub-base or
wall plate). Let the circuit be completed through the meter and after
allowing the unit to operate for about a minute take your reading. This
will assure you that the entire load that affects the cycling rate of
your system will be accounted for and you can correctly set the “heat
anticipator. I have previously discussed the proper method of setting
anticipators in previous issues of “Sales Bytes”
These sums up some of the questions this month- keep them coming. I
enjoy hearing from you.

Getting Your
Hands On a Hot Surface Igniter…Does It Matter?
November
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
Tell me about the physical handling of Hot Surface Igniters (HSI). Will
the oil from your fingers, when you handle the igniter by the heated
end, cause premature failure of the igniter?
Answer-
My assumption, of course, is that when you try to handle it, the
"business end" has cooled down or has not been energized at all ( if not
, call 911 ). I have a letter from Norton, to me, (dating back to at
least 18 or 19 years ago) that flatly states that the oil from your
fingers and hands will not cause failure of their "HSI" devices. In
fact, the oil will quickly vaporize as the unit heats-up. A popular
miss-conception- we hear this story repeatedly and we try to "knock it
down " when the opportunity arises.
Code requirements for these igniters specify that they must reach a
temperature of a minimum of 1000 degrees Centigrade or 1832 degrees
Fahrenheit (with 102 Vac applied) in order to safely ignite gas. The
upper limit of 132 Vac will produce a temperature of approximately 3100
degrees F while the normal voltage input of 120 Vac produces
approximately 2600 to 2650 degrees F temperature of the Silicon Carbide
material used in the manufacture of these units. Safety devices are
limited to working between 120 Vac (plus 10% or minus 15 %) or 102 Vac
and 132 Vac.
It may also be of interest that (because the Silicon Carbide - in
igniter form is quite fragile) the igniter must be handled with care. It
also must be noted, for safety's sake, that the ceramic holder remains
extremely hot -even when the igniter portion of the unit seems to have
cooled. Caution must be exercised when you are checking for
contamination on the igniter portion or for cracks or other damage that
may have occurred during the life of the device. A brilliant "hot spot"
on the igniter, when it is energized, indicates a crack or break in the
Silicon Carbide ' If the igniter is used for only ignition purposes (not
for both ignition and flame rectification) you may be able to (for a
very short period of time) continue to use the "HSI" for only ignition -
it's life will be very limited, however. When that condition exists and
you are using the "HSI" for both ignition and flame sensing - you MUST
replace the igniter with a like device. Flame rectification demands a
completely, fault free device, in order to function properly as a flame
conductor and sensor.

Millivolt
and 24 Volt Thermostats Are Different…or Sometimes Not
December
2007 issue
Real world suggestions for the residential
Service Technician from Bill Ribble,
40-year Honeywell veteran and controls expert.
Bill can be reached at 281-537-2701 or
threesons1@peoplepc.com
Question:
My customer had a thermostat problem and he replaced the device with a
Honeywell round mercury switch thermostat. He called and said the burner
doesn't come on like it should and sometimes it stays on far too long.
He called for help. When I got there I found that he had an old, thin,
flat, millivolt combination pilot and generator. The pi |