|
Part 1 of 2
The days of the old galvanized flue
pipe vented into a masonry chimney lined or unlined are quickly
fading away. It will not be long unit even Type “B” double wall gas
vent will be a thing of the past.
With increased efficiencies in equipment the requirements for
“special venting” are now in place, and venting requirements for 90+
efficiency products are likely to continually change.
Warnings like this in Installation and Operation manuals are
commonplace:
WARNING
FAILURE TO VENT THIS BOILER IN ACCORDANCE WITH THESE INSTRUCTIONS
COULD CAUSE FLUE GAS TO ENTER THE BUILDING RESULTING IN SEVERE
PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH:
• Do not
attempt to vent this boiler with galvanized, PVC, or any other
vent system not listed in the instructions.
• Do not attempt to mix components from different approved vent
systems.
• Do not obtain combustion air from within the building.
• Do not install a barometric damper or drafthood on this
equipment.
CAUTION
Moisture and ice may form on the surface around the vent
termination.
In talking to manufacturers reps about problems they discover on new
installations they tell me that most are improperly vented due to
failure to read the installation directions. We all know what
INSTALLATION INSTRUCTIONS are…we use them to set our coffee cups and
soda cans on so we don’t mark the equipment!
I am not going to attempt to teach Category IV 90+ Modulating
Condensing venting here. I simply want to point out some of the
typical things to watch out for. It is first of all imperative that
directions be followed. Here are some of the things most
manufacturers have in their instructions.
A lot of equipment today will list several different ways to vent
their product:
1.
Horizontal Side Wall Concentric Vent – the vent exits the
building through the outside wall. Concentric pipe is a “pipe
within a pipe”. Flue gas exits through the inside pipe, air for
combustion is drawn in around the space between the inner and
outer pipe.
2. Horizontal Side Wall Double Pipe (Separate flue gas pipe out
and another pipe for air in)
3. Vertical Double Pipe vent exits the building through the
roof. (Separate flue gas pipe out and another pipe for air in)
In some
cases they may be direct vent or they may be classified mechanical
exhausting. There are different requirements for those as to
termination outside the building. We will cover some of those later
in one of the other parts of this article.
Two basic categories:
1.
Concentric
2. Double Pipe (Separate flue gas pipe out and another pipe for
air in)
There are
usually requirements for maximum vent and air intake lengths as well
as in some cases minimum lengths.
Vent terminals vary with manufacturers and are not interchangeable
from manufacturer to manufacturer.
The most difficult and often the most troublesome is the vent
termination itself. This will be covered next month in Part 2 of
Venting Today – A Complex Subject.
These technical manuals are now available:
•
Circuitry and Troubleshooting Volume I and Volume II. $75.00 for
Volume I and $35.00 for Volume II + $10.00 S/H.
• New Edition of FUNDAMENTALS OF GAS VOLUME I. $75.00 + $10.00
S/H.
• FUNDAMENTALS OF GAS Volume II, which covers “Air for
Combustion” and “Venting” it is up to date with the latest
changes to the Fuel Gas Code Book. $75.00 + $10.00 S/H.
We also
conduct seminars on the following topics and many others:
•
Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
For
information call Tim McElwain at 401-437-0557, email him at
gastc@cox.net,
or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915

Venting Today - A Complex Subject
by Tim
McElwain
Part 1 of 2
One of the most difficult and often
troublesome aspects of the new venting when venting out the side of
buildings or even through the roof is vent termination or vent
location. When we go to the code books it gets very detailed for
example in the National Fuel gas Code ANSI Z223.1/NFPA 54 section
12.3.5 for direct vent appliances and concerning termination of
direct vent section 12.9.3.
For Mechanical Exhausting the rules for termination are different as
per section 12.4.3.6 concerning no vent terminating less than 7 feet
above grade where located adjacent to public walkways.
Many times the Direct Vent rules and the Mechanical Exhausting rules
get mixed up and incorrect venting termination occurs. Section 12.9
Through the Wall vent Termination covers all aspects of both direct
vent (12.9.3) and mechanical exhausting (12.9.1 and 12.9.2) We will
address those in Part Three of this article.
Some of the typical requirements:
-
Vent
terminal must be at least 1 foot from any door, window, or
gravity inlet into the building.
-
The
double pipe (Example: The vent and air intake terminals must be
at the same height and their center lines must be between 12 and
36 inches apart. Both terminals must be on the same wall)
-
All
terminal bottoms must be 12 inches above normal snow line or no
less than 12 inches above grade. (Note: it is often difficult to
determine normal snow line)
-
7 feet
above public walkway
-
Do not
install directly above windows or doors
-
The
bottom of the vent terminal must be at least 3 feet above any
forced air inlet located within 10 feet.
-
A
horizontal distance of at least 4 feet between the vent terminal
and gas meters, electric meters, regulators and relief
equipment. Do not install vent terminal over this equipment dues
to condensate.
-
Do not
locate vent under decks.
-
Top of
vent terminal must be at least 5 feet below eves, soffits, or
overhangs. Maximum depth of overhang is 3 feet.
-
Vent
terminal must be 6 feet from an inside corner.
-
Be aware
that condensate may freeze and cause damage to structures
nearby.
-
Install
vent termination away from prevailing winds in excess of 40 MPH.
-
Air
intake must not be near possible combustion air contaminants.
These are some of the termination
rules for sidewall venting. When vertical termination is allowed
there are other rules these will be covered in Part Three in next
month’s Sales Bytes.
We are now offering our latest manuals Circuitry and Troubleshooting
Volume I and Volume II. They are selling for $75.00 for Volume I and
$35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their second printing. The first
one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a
copy + $10.00 shipping and handling. In addition we also have
FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and
“Venting” it is up to date with the latest changes to the Fuel Gas
Code Book. It is also being offered at a price of $75.00 + $10.00
shipping and handling.
We also conduct seminars on the following topics and many others:
-
Fundamentals of Gas
-
Circuitry and Troubleshooting
-
Hydronic
Controls
-
Electric
Ignition Systems
-
Advanced
Electric Ignition Systems
-
Powerpile Systems
-
NEW
COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are interested in information
call 401-437-0557 or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail
gastc@cox.net

Venting Today - A Complex Subject
by Tim
McElwain
Part 3 of 5
This is the final article on the
minimum venting including requirements and exclusions.
As was mentioned in Part two we want to address the code
requirements for vent termination. We are looking at the National
Fuel Gas Code ANSI Z223.1/NFPA 54 2006 version and also the
International Fuel Gas Code 2006 version.
This section will cover some of the code requirements, which must be
addressed by manufacturers when setting down the rules for
installation. The code rules can be added to but never made less
severe in their application. It is however important note that
manufacturers installation requirements have precedence.
In the NFPA 54 code this is addressed in Section 12.9 on page
54-102. In the IFGC section 503.8 page 85. There is also a reference
to and Appendix “C” which is an illustration showing the application
of some of these rules.
To keep it simple we will refer to the NFGC section 12.9, keep in
mind the international code in this instance is exactly the same as
the national. I have also removed the metric measurements for
simplicity.
12.9 Through the Wall Vent Termination.
Section 12.9 provides requirements for separation of the
termination point of the venting systems from the building openings
for venting systems that terminate through the side of the building.
The concern is for recirculation of products of combustion back into
the building. There is also the possibility of cross contamination
of the fresh intake air for combustion to the equipment.
12.9.1 A mechanical draft venting system shall terminate at least 3
feet above any forced air inlet located within 10 feet.
Exception No. 1: This provision shall not apply to the
combus¬tion air intake of a direct-vent appliance.
The intent of 12.9.1 is to prevent gases from being drawn back into
the building. This requirement recognizes that vent gases are
lighter than air. Exception No. 1 recognizes that direct vent
appliance inlets do not communicate with air in a building.
Exception NO.2: This provision shall not apply to the separation of
the integral outdoor air inlet and flue gas discharge of listed
outdoor appliances.
Exception No. 2 to 12.9.1 prevents confusion in the installation of
outdoor gas appliances. Some authorities have misinterpreted the
code to prohibit such appliances or to require them to be modified
in the field, which is not the intent of 12.9.1. An example of this
type of appliance is a packaged rooftop air conditioner, which
incorporates a gas vent and a circulation air inlet used for
building air supply.
12.9.2 A mechanical draft venting system of other than direct-vent
type shall terminate at least 4 feet below, 4 feet horizontally
from, or 1 foot above any door, operable window, or gravity air
inlet into any building. The bottom of the vent terminal shall be
located at least 12 inches above grade.
A question that often comes up concerning section 12.9.2 is do
the separation requirements for exit terminals apply to windows that
do not open? In the 1992 revision to the code the word “window” was
replaced with “operable window”. This came about as a question
pertaining to picture windows, which do not open. So the section
does not apply to any windows, which cannot be opened.
12.9.3 The vent terminal of a direct-vent appliance with an input of
10,000 Btu/hr or less shall be located at least 6 inches from any
air opening into a building, and such an appliance with an input
over 10,000 Btu/hr but not over 50,000 Btu/hr shall be installed
with a 9 inch vent termination clearance, and an appli¬ance with an
input over 50,000 Btu/hr shall be at least a 12 inches vent
termination clearance. The bot¬tom of the vent terminal and the air
intake shall be located at least 12 in. (300 mm) above grade.
Sections 12.9.1 and 12.9.2 are concerned with preventing equipment
combustion products from being drawn into a building through fresh
air inlets, including operable windows (windows which can be
opened).
Subsection 12.9.3 permits the vent terminals of direct vent
appliances to be located much closer to air inlets than is provided
for with mechanical draft equipment. There is often a mis
application of rules for mechanical draft to direct vent equipment.
The vent gases from direct vent equipment disperse rapidly upon
leaving the vent terminal, even when the terminal is located under
an open window. However, a window is unlikely to be open when heat
is needed.
12.9.4 Through-the-wall vents for Category II and Category IV
appliances and noncategorized condensing appliances shall not
terminate over public walkways or over an area where condensate or
vapor could create a nuisance or hazard or could be detrimental to
the operation of regulators, relief valves, or other equipment.
Where local experience indicates that condensate is a problem with
Category I and Category III appliances, this provision shall also
apply.
Subsection 12.9.4 provides for the protection of persons and
equipment, including gas meters. It places responsibility on the
installer to locate vent termination for Category II and Category IV
appliances away from walkways and gas equipment. It also recognizes
that any appliance can present a condensation problem in a cold
climate.
High-efficiency condensing appliances have a seasonal efficiency of
90 percent or higher, which reduces vent gas temperatures to a point
where the water vapor produced as a product of combustion condenses
to liquid water in the appliance or in the vent. These condensing
appliances carry a vented appliance category of Category IV. This
type of appliance produces much cooler vent gases, resulting in
water condensing in the vent. Venting must be accom¬plished with a
fan, because the vent gases are not hot enough to operate the
natural draft vent. Water will condense in the vent and will
dissolve some of the gases produced during combustion, which are
slightly acidic. The vent materials used with these appliances must
be able to resist the acidic condensate. For many of these Category
IV appliances, plastic vent material is acceptable and preferred for
corrosion reasons. The appliance manufacturer specifies the vent
material for use with Category IV appliances.
The advantage of high-efficiency appliances is that they
significantly reduce the amount of gas consumed with no loss in
output. A mid-efficiency appliance uses one-third less gas than a
conventional appliance, and a condensing appliance uses only
one-half of the gas of a conventional appliance. The savings in fuel
are offset by higher first cost and the higher maintenance
requirements of high-efficiency appliances, as well as the added
cost of the electricity to operate the fan.
In the next part (Part 4) we will
address other requirements for venting in particular vertical
venting.
In part 5 we are going to address the venting categories mentioned
in this article.
We are now offering our latest manuals Circuitry and
Troubleshooting Volume I and Volume II. They are selling for $75.00
for Volume I and $35.00 for Volume II + $10.00 shipping and
handling.
We have two OTHER NEW manuals in their second printing. The first
one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a
copy + $10.00 shipping and handling. In addition we also have
FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and
“Venting” it is up to date with the latest changes to the Fuel Gas
Code Book. It is also being offered at a price of $75.00 + $10.00
shipping and handling.
We also conduct seminars on the following topics and many others:
• Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are interested in information call 401-437-0557 or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail
gastc@cox.net

Venting Today - A Complex Subject
by Tim
McElwain
Part 4
With this continuing discussion on
venting of Modulating/Condensing equipment it is once again not the
purpose of this article to define exact installation requirements.
The attempt here is to address some typical types of requirements
for venting this equipment.
When vertical venting is an option on this equipment it is important
to follow manufacturers rules as to EQUIVALENT LENGTH as it relates
to air intake of vent. An example would be:
90-degree concentric elbow 4.5 feet
45-degree concentric elbow 4 feet
A 3” 90 degree elbow 5.5 feet
A 3” 45 degree elbow 4 feet
Many times failure to observe these equivalent lengths in
calculating the maximum length of the vent can result in inadequate
air supply or problems with the pressure switch not making. It is
often a good idea if the system will not work with the vent
connected to remove the vent temporarily and see if the equipment
will operate with it disconnected. If it will and it will not work
with it connected you obviously have a problem with the vent. One of
the things to address is length and also equivalent lengths of
fittings. There may also be other problems such as blockage or
damage to the vent.
There may also be other requirements addressed in the following
examples:
Permitted Terminals for Vertical Venting - A straight
termination is installed in the end of the vent pipe. The air inlet
terminal consists of a 180-degree elbow (or two 90 degree elbows)
with a rodent screen. Vent manufacturer part numbers for these
screens vary.
Vertical Vent Terminal Locations - Observe the following
limitations on the location of all vertical vent terminals.
• The
top of the vent pipe must be at least 2 feet above any object
located within 10 feet.
• The vertical distance between top of the vent and air inlet
terminal openings must be at least 12".
• The bottom of the air inlet terminal must be at least 12"
above the normal snow accumulation that can be expected on the
roof.
• The air intake terminal must be located on the roof and must
be no further than 24" horizontally from the exhaust pipe.
Wall
thimbles - Wall thimbles are often required where single wall
vent pipe passes through combustible walls.
Pitch of Horizontal Piping - Pitch all horizontal piping so
that any condensate, which forms in the piping, will run towards the
boiler:
• Pitch
horizontal concentric venting 5/8" per foot
• Pitch Stainless steel venting 1/4" per foot.
Supporting Pipe - Vertical and horizontal sections of pipe must
be properly supported:
•
Support concentric venting near the female end of each straight
section of pipe.
• Support stainless steel venting as called for by the vent
manufacturer's instructions.
The next
article on this topic will cover some of the code requirements,
which must be addressed by manufacturers when setting down the rules
for installation. The code rules can be added to but never made less
severe in their application. It is however important to note that
manufacturers installation requirements have precedence.
We are now offering our latest manuals Circuitry and Troubleshooting
Volume I and Volume II. They are selling for $75.00 for Volume I and
$35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their
second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME
I it is priced at $75.00 a copy + $10.00 shipping and handling. In
addition we also have FUNDAMENTALS OF GAS Volume II, which covers
“Air for Combustion” and “Venting” it is up to date with the latest
changes to the Fuel Gas Code Book. It is also being offered at a
price of $75.00 + $10.00 shipping and handling.
We also conduct seminars on the following topics and many others:
•
Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are
interested in information call 401-437-0557
or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail
gastc@cox.net

Venting Today - A Complex Subject
by Tim
McElwain
Part 5
You can use the chart below to
determine the equipment’s venting category. Look at the equipment’s
rating plate and then proceed down that column to determine
requirements and perimeters for venting that particular category.
For example, a listed Category I appliance can be vented using a
Type B gas vent, chimney, single-wall metal pipe, chimney lining
system that is listed for gas venting, or a special gas vent listed
for the appliance. The chart refers to appliance Category I through
Category IV. The categories are based on vent temperature and
pressure.
The term non-positive vent (negative pressure) means that even if
fans or blowers are used in an appliance or vent system, venting is
accomplished by natural draft. Natural draft is created by
temperature difference (delta T) and the height of the vent. (The
vent pressure is lower than atmospheric).
The term positive vent pressure means that fans, blowers or other
means are used to propel vent gases through the vent at above
atmospheric pressure.
Note that the definitions reference "a vent gas temperature that may
cause excessive condensate production in the vent.") A specific
temperature is not provided, because it is not the same for all
appliances. The ANSI Z21 standards for appliance categorization can
be referenced for this information. Annex L contains a complete list
of the ANSI Z21 standards. Note that the installer should not need
this information, since the appliance vent category is included in
the appliance manufacturer's installation instructions and on the
appliance nameplate. The criteria in the ANSI Z21 standards are
based on a flue loss of 17 percent of total energy. The 17 percent
flue loss is the same flue loss built into the vent sizing tables
for fan-assisted appliances. In this way, the standards ensure that
the appliance will work properly with the vent system. The term
nonpositive vent pressure means that the pressure in the vent
will be lower than the surrounding atmosphere if the vent system
meets the requirements of the National Fuel Gas Code Chapter 12 and
Chapter 13. The incorporation of a fan into the appliance does not
always mean that the vent pressure is positive. If unsure, check the
appliance nameplate or manufacturer's instructions for the venting
category, or check the vent pressure with a manometer or other
pressure gauge when the appliance is operating.
|
VENTING
CATEGORIES: |
GAS-FIRED EQUIPMENT |
|
Operating
|
|
|
|
|
|
|
characteristics |
Category I |
Category II |
Category III |
Category IV |
|
Pressure in
the vent |
Negative |
Negative |
Positive |
Positive |
|
Temperature
of |
Above |
Below |
Above |
|
Below |
|
vent gas
(4) |
275°F |
275°F |
275°F |
|
275°F |
|
Annual
efficiency |
Below 84% |
Above 84% |
Below 84% |
Above 84% |
|
Condensation |
Not acceptable |
Possible |
Possible |
In heat |
|
|
(1)
|
(in vent) |
(3) |
|
exchanger |
|
Design requirements
|
|
|
|
|
|
Gas (air)
tight vent |
No |
No |
Yes |
|
Yes |
|
Corrosion-resistant |
No (1) |
Yes |
Possible |
(3) |
Yes |
|
vent (water
tight) |
|
|
|
|
|
|
Vent into
|
Permitted |
No |
No |
|
No |
|
masonry
chimney |
(1) and (2) |
|
|
|
|
|
Combined
venting |
Permitted |
No |
No |
|
No |
|
Condensate
drain |
No |
Ask |
Possible |
(3) |
Yes |
|
|
|
manufacturer |
|
|
(At |
|
|
|
|
|
|
equipment) |
|
Source of
|
N.F.G.C. |
Manufact. |
Manufact. |
Manufact. |
|
information
|
Fuel gas code, |
literature |
literature |
literature |
|
heating equipment
|
|
|
|
|
|
|
and vent system |
|
|
|
|
|
|
manufacturers |
|
|
|
|
NOTE 1 Usually, there is no problem when high vent gas
temperature equipment is vented into double-wall vent or into a
lined masonry chimney; but condensation could occur if
mid-efficiency (80% to 84%) mechanical draft equipment is vented
into a vent that has highly conductive walls, cold walls, or massive
walls. In this case, design a vent system that minimizes the wall
losses (use double-wall pipe for the whole run and avoid long runs
through cold spaces).
NOTE 2 Install either a rigid or flexible metal liner inside
of the masonry chimney and use a double-wall connector when venting
mid-efficiency (80% to 84%), me¬chanical draft equipment.
NOTE 3 Condensation in the vent is posing on the ambient
temperature and the conductivity of the vent walls. In this case,
design a vent system that minimizes the wall losses (use insulated
pipe and avoid long runs through cold spaces). A corrosion-resistant
flue and a drain may be required if condensation cannot be prevented
- refer to the manufacturer's recommendations.
NOTE 4 The dewpoint of the vent gas depends on the fuel
(natural or LP gas), the amount of excess air and the amount of
dilution air. The limiting case occurs when the dewpoint of the vent
gas is at a maxi¬mum, which is about 135°F. This maximum is produced
when natural gas is burned with no excess air or dilution air.
There¬fore 275°F = 135°F dewpoint + 140°F
It is a good rule of thumb when looking at vent temperature that any
temperature from 300° (F) down is a concern for condensing and needs
to be addressed in the case of Category I and III venting.
We are now offering our latest manuals Circuitry and Troubleshooting
Volume I and Volume II. They are selling for $75.00 for Volume I and
$35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their
second printing. The first one is titled FUNDAMENTALS OF GAS VOLUME
I it is priced at $75.00 a copy + $10.00 shipping and handling. In
addition we also have FUNDAMENTALS OF GAS Volume II, which covers
“Air for Combustion” and “Venting” it is up to date with the latest
changes to the Fuel Gas Code Book. It is also being offered at a
price of $75.00 + $10.00 shipping and handling.
We also conduct seminars on the following topics and many others:
•
Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are interested in information
call 401-437-0557 or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail
gastc@cox.net

Venting Today - A Complex Subject
December 2007 issue
by Tim
McElwain
Part 6
Plastic Piping:
• The Code
• Product Recall
• The Effects of Temperature on PVC pipe
National Fuel Gas Code specifies that plastic piping used for
venting appliances listed for use with such venting materials shall
be approved.
Before the introduction of high-efficiency (90 + percent efficiency)
gas utilization equipment, plastic piping was prohibited as a vent
material. High-efficiency (Category IV) appliances reduce vent
temperatures, resulting in condensate formation. As accumulation of
condensate can become a source of corrosion of metal vents, plastic
piping became the preferred material. Paragraph 12.5.2 of the
National Fuel Gas Code requires that plastic vent materials be used
for listed gas utilization equipment only when specified in the
manufacturer's instructions.
Section 12.5.3 of the National Fuel Gas Code Special Gas Vent
Special gas vent shall be listed and installed in accordance with
the special gas vent manufacturer's installation instructions.
All special gas vents are listed vent materials. Special gas vents
are listed in accordance with UL 1738, Standard for Venting
Systems for Gas-Burning Appliances, Categories II, III and IV.
Installation instructions for special gas vents include limitations
on operating temperature, categories of appliance to be used with
each vent, clearance to combustible materials, types of fittings and
joint sealant to be used, and vent termination requirements.
Special attention should be given to the following areas:
1. Proper support for the special gas vent to prevent sagging and to
allow for expansion, contraction, and condensate drainage
2. Proper cutting and cleaning of joints and fittings, and the use
of recommended joint sealants (substitutes are not usually
permitted)
3. Construction of a condensate trap (see the appliance
manufacturer's instructions for special requirements)
4. Wall penetrations (the pipe should not be secured at a thimble,
because the pipe must be allowed to move to accommodate expansion
and contraction)
5. Insulation [the vent pipe or the fittings of the inside of a wall
thimble must not be insulated when polymeric (nonmetallic) vent
materials are used]
Product Recall
More than 15 years ago, a class of special gas vent known as "high
temperature plastic vent" (HTPV) was introduced to the market for
use with mid-efficiency appliances. Field experience has shown that
these vent systems are prone to failure. The failure may occur
because of improper installation practice and/or corrosion from
acidic condensate. At this time an active product recall is still
under way, with the cooperation of the U.S. Consumer Product Safety
Commission, appliance manufacturers, and the vent pipe
manufacturers. The product recall covers furnaces that are
horizontally vented, as well as all boiler installations. Those who
encounter one of these vent systems should call (800) 758-3688 for
information on how to proceed. This number is operated by the
product manufacturers and will be in operation until the recall is
substantially complete. If the number is not in operation, questions
can be referred to the furnace, boiler, or water heater
manufacturer.
To determine whether the installation has an HTPV pipe system that
is subject to this program, the vent pipes attached to the natural
gas or propane furnaces or boilers should be checked. Vent pipes
subject to this recall program can be identified as follows:
• The vent pipes are plastic.
• The vent pipes are colored gray or black.
• The vent pipes have the names "Plexvent," "Plexvent II," or "Ultravent"
stamped on the vent pipe or printed on stickers placed on pieces
used to connect the vent pipes together.
The location of those vent pipes should also be checked. For
furnaces, only' HTPV systems that have vent pipes that go through
the side walls of structures (horizonta1 systems) arc subject to
this program. Other plastic vent pipes, such as white PVC or CPVC
are not involved in this program.
The Effects of Temperature on PVC Pipe
Polyvinyl Chloride (PVC) is a thermoplastic, and as such, its
physical properties change with temperature variations Dimensions,
pressure capacity, and stiffness are all affected by temperature
changes. The published dimensions and performance ratings for PVC
pipe and conduit products are usually applicable only for 73°F. The
following will help to explain how PVC pipe and conduit products are
affected by operating temperatures other than 73°F.
Dimensions
Like all materials, PVC expands with increasing temperatures and
contracts with decreasing temperatures.
The coefficient of thermal expansion for PVC is: 3.0 x 10-5 in/in/°F
Because the length-to-diameter ratios of PVC pipe and conduit
products are generally very large, length change from temperature
variation is the most noticeable. A good rule of thumb in design of
PVC pipe and conduit systems is to allow 3/8" length variation for
every 100 feet of pipe for each 10°F change in temperature. (This
rule is independent of pipe size.) Table 1 can also be used to
determine the effects of temperature changes on the length of PVC
pipe and conduit.
NOTE:
THE MAXIMUM RECOMMENDED OPERATING TEMPERATURE FOR PVC PRESSURE PIPE
IS 140° (f)
FOR CPVC IT IS 200° (F)
This is reason enough to pay very close attention to flue gas
temperatures on a lot of 90+ condensing equipment.
We are now offering our latest manuals
Circuitry and Troubleshooting Volume I and Volume II. They are
selling for $75.00 for Volume I and $35.00 for Volume II + $10.00
shipping and handling.
We have two OTHER NEW manuals in their second printing. The first
one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a
copy + $10.00 shipping and handling. In addition we also have
FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and
“Venting” it is up to date with the latest changes to the Fuel Gas
Code Book. It is also being offered at a price of $75.00 + $10.00
shipping and handling.
We also conduct seminars on the following topics and many others:
• Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are interested in information call 401-437-0557 or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail gastc@cox.net

Venting Today - A Complex Subject
January 2008 issue
by Tim
McElwain
Part 7
More Plastic Piping:
As I continue my research on
venting materials and venting issues I find more and more a concern
of the use of plastics for venting. This discussion was to be only a
few articles when I started but has surely grown as I look further
into this issue of Special Venting.
I solicited some comments from Glenn Stanton the Manager of
Technical Development for Burnham Hydronics and U.S. Boiler Co.,
Inc. His comments are included here as to PVC venting.
The concerns expressed lie with several factors. The first of these
being that PVC and ABS Pipe and fitting manufacturers do not
necessary express approval for using these products for venting gas
byproducts and the ASTM standards hold no mention regarding the use
of venting and PVC. One or two companies that manufacture PVC pipe
and fittings have put out statements to the effect that they do not
recommend using it for venting gas combustion byproducts. The second
issue is that we, you or nobody else can guarantee that the pipe
your distributor stocks is solid core or foam core. Some
distributors stock one or the other based on primary demand and if
they did stock both that is no guarantee that they will have solid
core every time you order or that what is shipped to you is solid
core. There is a very strong likelihood of foam core pipe ending up
in many of these applications due to those reasons. The third issue
is that PVC is certified and approved for 140°F temperature for
"pressure applications". Mod/Con boilers can in fact exceed these
temperatures during high fire conditions with Domestic Hot Water
demands. The boilers have flue gas sensors that know this is
happening and will turn down the input or modulate to protect the
pipe. Reducing the boiler input when it needs to recover the heater
will lengthen that DHW recovery period. To what extent that happens
is a function of boiler sizing and demand? I too have seen a couple
of manufacturers that approve CPVC for the first several feet. But
the real question is.... How many distributors do you deal with that
actually carry 3" and 4" CPVC pipe and fittings in stock? The fourth
factor is there is more and more discussion these days about this
topic and the trend of the governing agencies uses verbage
referencing "Vent Systems". We see this with AL29-4C, Polypropylene
and Ipex. They are indeed "vent systems" that have been tested and
certified for venting applications. As mentioned, Canada has taken
action to discontinue the use of PVC and ABS and that any material
used for venting must be a "system" that conforms to their
standards. Our stance with our Freedom ™ CM and CHG boilers is to
use either AL29-4C or Polypropylene vent systems. These systems are
tested and certified for venting purposes and have temperature
tolerances far in excess of what you would expect with these
boilers. That's my story and I'm sticking to it..... and I will be
willing to bet that many other equipment manufacturers will begin to
see it that way too as thing progress in
Canada.
Then some recent information from Viessmann President Harald
Prell add to the discussion.
Venting of Residential Viessmann
Gas-Fired Condensing Heating Boilers
At present, there are industry
discussions in regards to venting of gas-fired condensing heating
boilers. The following represents the opinion and position of
Viessmann Manufacturing in regards to venting Viessmann gas-fired
condensing heating boilers, series Vitodens 200 and Vitodens 100.
Since the mid 80's, we manufacture and sell gas-fired condensing
heating boilers; now sold in more than 30 countries, including North
America. In almost all countries, PPS (polypropylene) is mostly used
in coaxial vent-type applications or stainless steel for single wall
venting systems. PPS is suitable for a steady flue gas temperature
of 250° F (121 ° C) and for short-term exposure up to 280° F (138°
C). Stainless steel vent pipe is suitable for 550° F (288° C);
typically, an SA240 316 L material is used or the higher grade in
North America AL29-4C.
Due to the fact that gas-fired condensing boilers are being vented,
not only the temperature of the flue gas becomes an important factor
but also, in combination with the extreme high moisture content, the
associated acidity (pH level) of the flue gas condensate and the
extreme temperature exposure to outdoor conditions need to be
considered when selecting materials.
PPS, as well as stainless steel venting systems, have successfully
been in use for many years and carry independent certifications for
venting these types of heating boilers properly.
CPVC material is certified for 90° C (194° F) and PVC is certified
for 65° C (149° F) according to ULC-S636 Standard for Type BH Gas
Venting Systems. The Viessmann gas-fired condensing heating boiler
Vitodens 200 and 100 series are approved for use with listed CPVC
material.
IPEX (the manufacturer of CPVC venting systems) informed that this
material is now readily available. Should there be supply issues,
please contact your Viessmann sales representative or Viessmann
directly- (in Canada at 1-800-387-7373 or in the U.S. at
1-800-288-0667).
My Comment: This next information I find very interesting and
certainly does not only apply to Viessmann equipmen only.
The flue gas temperature exiting a gas-fired condensing heating
boiler depends on a number of factors; some impact more than others:
1. The maximum allowable supply water temperature rating on the
heating boiler or the maximum adjustable aquastat or limit settings.
The Vitodens 200 is limited to a max. supply water temperature of
75° C (167° F) and the Viessmann Vitodens 100 series is limited to a
max. water supply temperature of 80° C (176° F), plus cut in and cut
off differential.
2. Venting with a coaxial vent pipe system, where fresh outside air
moves around the PPS pipe, preheats the combustion air and cools
flue gas temperature further.
3. The heating boiler utilizing one separate vent pipe and a
separate fresh air intake pipe.
4. Boiler utilizes standard room air for combustion air or outside
air directly.
5. Flue gas velocity within vent system (vent length and
restriction).
6. Possible vent restrictions (partial icing or blockage of vent
terminal and/or air intake).
7. Excessive wind and pressure impact on terminations.
8. Possible partial heat exchanger flue gas passageway blockage.
9. Cycling frequency pending on control strategy, system water flow,
zoning, etc.
After all of the above is considered, is there a safety margin left?
After all, reliability and dependability for heating comfort are key
factors in our opinion.
The main factor influencing flue gas temperature is however the
return water temperature to the heating boiler. This is the primary
influence on how high the flue gas temperature will go and exit into
the actual flue pipe.
Both models of Viessmann heating boilers are certified to ANSI
Z21.13 CSA 4.9 Low Pressure Steam and Hot Water Heating Boiler
Standard by CSA. The test procedure within this particular standard
calls for a boiler water supply temperature maintained until the
limit control functions ± 3° C (± 5° F). When the boiler is tested
under this criteria and a very low return temperature is selected
(by the manufacturer), it will drive the flue gas temperature
extremely low. Typically the flue gas temperature on both Viessmann
heating boilers is between 5° C (9° F) and 15° C (27°F) above the
return water temperature; therefore, for example, with a low return
water temperature selection of 27° C (80° F) into the boiler, a flue
gas temperature of 42° C (107° F) would be the net result. This flue
gas temperature would not pose a problem in general for any type of
PVC or ABS material; however, this test with a very large
temperature differential of 55° C (100° F) between supply and return
is not realistic. Also, at that temperature differential, the flow
rate through the boiler would only be 20% of the actual required
flow for a typical 99911 ° C (20° F) hydronic system design
temperature differential; again, not realistic in an everyday
install.
Example under full input - design condition:
If the boiler water supply temperature would be 82° C (180° F),
provided the boiler is certified to that temperature, then one would
typically assume a temperature differential of 11 ° C (20° F) and
therefore the return water temperature would return back at 71 ° C
(160° F) to the heat exchanger. The dew point of natural gas is 57°
C (135° F) at sea level.
The boiler would not condense anymore and the stack temperature
would certainly be higher than the return water temperature of 71 °
C (160° F). It would probably reach the 85° C (185° F) to 88° C
(190° F) mark.
This operating condition now clearly shows flue gas temperatures
higher than what the limit is on standard PVC, CPVC and ABS. Even if
the heating boiler has a limit at 71 ° C (160° F) set for the boiler
water supply temperature and an 11 ° C (20° F) spread to the return
water temperature, the return temperature would still be 60° C (140°
F). the flue gas temperature could exceed the maximum listed
temperature limits.
Especially when heating boilers are utilized to provide domestic hot
water through an indirect ¬fired domestic hot water storage tank,
return temperatures back to the boiler, when the tank temperature
reaches 60° C (140° F), will rarely be less than 60° C (140° F) due
to obvious reasons and higher flue gas temperatures will be the
result again.
In our evaluation for suitable vent pipe material, we have looked at
the following data:

This, in our technical opinion, renders standard PVC, CPVC and ABS
unfit for venting a Viessmann Vitodens 200 or Vitodens 100 series
gas-fired condensing heating boiler. Also, the Canadian Gas Fired
Equipment Installation Code CSA B 149.1 has already prohibited the
use of this material. Furthermore to our knowledge, no manufacturer
of DWV (drains, waste, vent) PVC had it certified or recommends this
material as a vent pipe for gas-fired condensing heating boilers.
DWV approved materials are mostly used in sewer and drainage
applications within buildings or below ground. These materials are
not subject to this type of temperature (erratic temperature
changes) with constant pH levels between 3 and 4, and none of these
materials are typically exposed to long periods of ultraviolet light
or severe cold outdoor temperatures, when used in vent terminations
where all the foregoing conditions occur at the same time. In
addition, the expansion factor of the pipes has to be considered,
possible change of support, including feasibility of adhesives and
terminations.
As high limits and low water cutoffs are safety measures for the
pressure vessels, so is venting the safety measure for disposing
flue gas.
A venting system will become part of a home. It may get enclosed in
a wall or a ceiling and therefore not be easily accessible in the
future for inspection.
For the reasons mentioned above, Viessmann does not recommend and is
not certified on the Vitodens 200 and Vitodens 100 series with DWV
PVC, CPVC or ABS, even though our listed efficiencies are some of
the highest in the industry.
PVC, CPVC and ASS may only be used for the combustion air intake
side when a separate pipe is used for the combustion air intake
system and the separate flue gas pipe is constructed utilizing
stainless steel or CPVC ULC-S636.
We recommend, and are approved for, venting and combustion air
intake with a coaxial PPS / aluminum venting system for combined
venting and combustion air supply.
For separate flue gas venting, both heating boilers are approved
with CPVC 90° C (194° F) according to ULC-S636 or AL29-4C stainless
steel venting, in combination with DWV PVC, CPVC, ASS or even
galvanized sheet metal ducting for the separate air intake for
combustion air. Of course, CPVC, ULC-S636 or stainless steel may
also be used for the air intake side.
We have opted not to employ a fixed flue gas temperature sensor,
with manual reset, to avoid boiler lockout when high flue gas
temperatures occur to protect a venting system, in order not to
subject our customers to boiler lockouts in the main heating season
when higher water temperatures are required to maintain the heating
comfort. Instead, we have selected, in our opinion, the correct
venting material for the Vitodens 200 and Vitodens 100 series.
For more information, please contact the technical department at
Viessmann in Waterloo 1-800-387-7373 or Warwick 1-800-288-0667.
Stay tuned as we look for more information on special venting.
We are now offering our latest manuals Circuitry and Troubleshooting
Volume I and Volume II. They are selling for $75.00 for Volume I and
$35.00 for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their second printing. The first
one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a
copy + $10.00 shipping and handling. In addition we also have
FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and
“Venting” it is up to date with the latest changes to the Fuel Gas
Code Book. It is also being offered at a price of $75.00 + $10.00
shipping and handling.
We also conduct seminars on the following topics and many others:
•
Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are interested in information
call 401-437-0557 or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail
gastc@cox.net

Air for
Combustion and Ventilation a New Subject- Part One
February 2008 issue
by Tim
McElwain
After our recent series on Venting and
in particular “Special Venting” it is also important to address the
need for air for combustion and ventilation. On many of my
consulting calls I find that the contractor or technician has
overlooked the importance of insuring adequate air for combustion.
It is often the case that the homeowner has done some remodeling and
has overlooked the fact that what was once a full open basement is
now cut in half or even worse the boiler or furnace along with the
water heater are now in a small tightly confined space with
absolutely no provision for air. Here is an example of what is a
full basement and what air requirements there are.
PROBLEM:
RANCH HOUSE 25' X 40' with cellar ceiling 8' high 40 x 25 x
8 = 8,000 cubic feet of space
NATIONAL FUEL GAS CODE: 50
cubic feet of air for every 1,000 btu's
8000
50 = 160 x 1,000 = 160,000 btu's
House Heater =
100,000 Btu's
+ Water Heater =
35,000 Btu's
+ Dryer =
30,000 Btu's
=
165,000 btu’S
For all practical purposes because the Btu's exceed 160,000
this is a CONFINED SPACE and air must be brought from
outdoors.
So as we will see in these articles
more air may be needed.
The changes to the 2002 National Fuel
Gas Code reflected the need for more careful calculations for
Combustion Air. The procedures remained pretty much the same in the
2006 code. The revision provides five different procedures for
supplying combustion air:
1. 100
percent indoor air
2. 100 percent outdoor air
3. A combination of indoor and outdoor air
4. An engineered system
5. A mechanical air supply.
The objective it seems is to provide
technically based methods for calculating required indoor air volume
for all structures, including those with very low air infiltration.
In Figure 1 from AGA the different methods are shown.

Figure 1 Methods of determining Air
for Combustion
In order to make the code more
flexible there are now two ways to calculate the required indoors
air volume. This is especially important when a building is designed
for low air infiltration.
The method that has been in the code for many years is retained and
is called the Standard Method (50 cubic feet of volume per 1,000
Btu). This method can be used for buildings that have a 0.40 air
change per hour (ACH) or higher air infiltration rate. The new
method, Known Air Infiltration Rate Method (KAIR), can be used when
the structure's air infiltration rate is blown or estimated, or when
the structure has less than 0.40 ACH.
An important feature of KAIR is that it recognizes the difference in
combustion air volume requirements between the two appliance types,
fan-assisted appliances and other than fan-assisted appliances,
which is "all other appliances." The amount of required indoor air
for each equipment type is different due to the different amounts of
dilution air that each requires. If installations include both
equipment types, required air volume is calculated separately for
fan-assisted and for other than fan-assisted appliances.
Prior to the 1984 edition, the code requirements for indoor
combustion air did not provide guidance for "unusually tight
construction." In the 1984 edition, a requirement was added stating
that if indoor combustion air was used and if the construction was
unusually tight, outside combustion air had to be provided. This
requirement addressed valid concerns that buildings were being built
to minimize air infiltration since the energy crisis of the 1970s.
Although this addition provided no guidance on what unusually tight
construction is, the addition provided a positive step toward
addressing the meaning of the term.
In the 1988 edition, a definition of unusually tight construction
was added, which included three items:
1. Walls
and ceilings exposed to the outside atmosphere have a continuous
water vapor retarder with a rating of 1 perm or less with
openings gasketed or sealed.
2. Weather stripping has been added on open able windows and
doors.
3. Caulking or sealants are applied to areas such as joints
around window and doorframes, between sole plates and floors,
between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical, and gas lines, and at
other openings.
A further
revision to the definition was added in the 1999 edition, adding a
fourth item to the definition of unusually tight construction
4. The
building has an average air infiltration rate of less than 0.35
air changes per hour.
The fourth item provided additional
guidance and changed the definition to not automatically include all
new construction but to base the need for outdoor combustion air on
the actual air infiltration rate.
The 2002 edition of the code goes further by eliminating the
definitions of unusually tight construction, confined space,
and unconfined space and providing two methods to determine
the amount of indoor volume needed for buildings with varying air
infiltration rates. The code is also now clearer as to what
conditions are needed to mandate the use of additional outside
combustion air, which many jurisdictions had not applied uniformly.
Some jurisdictions considered all new structures built to a model or
state energy code to be inherently unusually tight.
The terms confined space and unconfined space were
eliminated because they no longer denote one single value (50 cubic
feet per 1,000 Btu) but varying volumes, depending on the method
used and the amount of air infiltration. A new term, required
volume, is used to better describe the revised code's intent.
Required volume does not require a definition.
Other changes include the following:
The combination outdoor/indoor combustion air provisions have been
simplified and revised to allow the use of a single high outdoor
opening. The section was simplified to improve its applicability.
The former coverage was nearly impossible to follow and explain. The
revised coverage allows the use of a one single high mounted outdoor
opening when the combination outdoor/indoor combustion air openings
method is used. The previous code only allowed the use of two
outdoor openings, one high and one low, which severely restricted
the usefulness of this method. Because previous GRI research
demonstrated the viability of the single high outdoor opening (for
all air from the outdoors), it is logical to extend its feasibility
to the combination of outdoor/indoor coverage adopted by the code in
1999.
Three new combustion air tables were added to provide users with the
calculated values without the need to perform calculations for the
required air volumes under the Standard and KAIR methods.
The importance of combustion, dilution, and ventilation air, as
shown in Figure 1 cannot be overemphasized. Typical gas-fired
natural draft (draft hood) furnaces require approximately 21cubic
feet of air (i.e., combustion, vent dilution, and ventilation) for
every cubic foot of gas burned. Although modern fan-assisted
combustion system furnaces do not need dilution air, they still
require approximately 15 cubic feet of air for each cubic foot of
gas burned. This amount of air can range between 1500 cubic feet per
hour and 2100 cubic feet per hour for each 100,000 Btu/hr of gas
input. This air is needed to support the combustion and venting
process of the appliance and to provide ventilation cooling for the
casing and internal controls. This instruction will help the reader
determine the proper method for meeting these requirements. (See
Figure 3)


It is important to note that due to
all of the changes in gas equipment in the last few years that air
for combustion requirements must change to meet these new
requirements. Certainly increased efficiencies and the use of fan
assisted combustion systems prompted these changes in order to meet
the demands of this new equipment. A training session conducted by
the Gas Research Institute at the New England Gas Association
Operations School conducted at Bentley College in Massachusetts in
1994. At that session they introduced changes that resulted from
research they conducted and reported in 1994. The report noted that
a single opening to the outdoors could be used if certain
qualifications were met. We will discuss this in detail later in
this instruction. The 1996 code implemented this one opening
procedure as part of the code. Then the (1999) added some language
to the code that allows the reduction of the two openings to
outdoors. This can be accomplished if the indoor space in which the
equipment is located can contribute part of the needed air.
Air for combustion, ventilation, and dilution of flue gases for gas
equipment installed in buildings is to be obtained by applying one
of the methods covered in Figure 1. When indoor air is not
sufficient then one of the other methods must be applied.
There are some exceptions to these requirements, they are that they
cannot be applied to direct vent appliances. The other exception is
Type I (residential) dryers that are provided with make up air.
There will be a special section concerning make up air for dryers
and information on air requirements and the affect of dryers on
combustion air.
All equipment other than Category I and natural draft appliances
must have combustion, ventilation, and dilution air. The procedures
for providing that air will be covered in the manufacturers
directions. The determination as to what appliances are being
referred to are those with power vents, either a part of the
equipment or added on to the equipment, clothes dryers, and high
efficiency furnaces (above 95%).
All equipment must be installed so as to not interfere with proper
circulation of air.
If draft hoods or barometric are used they must be in the same room
as the equipment. This is to prevent the possibility of different
pressures.
A provision should be made for make up air to compensate for exhaust
fans, attic fans, kitchen ventilation systems, clothes dryers and
fireplaces, The operation of these systems can create a difference
in pressure in the building. The result of that pressure difference
is that combustion gases may spill into the dwelling from the draft
hood or barometric creating a hazardous condition. This in
conjunction with insufficient air for combustion and ventilation can
cause incomplete combustion. The result being flame rollout and the
possibility of high levels of Carbon Monoxide.
This instruction contains provisions intended to provide adequate
combustion and ventilation air for gas appliances based on an air
infiltration rate of one-half air changes per hour. Because of
increased interest in energy conservation, consumers are attempting
to reduce heat losses by adding weather-stripping, caulking, and
insulation to their residences. Although these measures are
effective in reducing energy consumption, they also can reduce the
air infiltration rate of the building to levels below those used to
determine proper combustion air. In these situations, additional air
must be provided for proper operation of the equipment. In these
tight buildings, the operation of exhaust fans can create negative
pressure in buildings. Air will enter the building through any
opening available, and the vent of a gas appliance may provide the
easiest available opening. An example of this is shown in Figure 4.

Figure 4
We are now offering our latest manuals
Circuitry and Troubleshooting Volume I and Volume II. They are
selling for $75.00 for Volume I and $35.00 for Volume II + $10.00
shipping and handling.
We have two OTHER NEW manuals in their second printing. The first
one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a
copy + $10.00 shipping and handling. In addition we also have
FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and
“Venting” it is up to date with the latest changes to the Fuel Gas
Code Book. It is also being offered at a price of $75.00 + $10.00
shipping and handling.
We also conduct seminars on the following topics and many others:
•
Fundamentals of Gas
• Circuitry and Troubleshooting
• Hydronic Controls
• Electric Ignition Systems
• Advanced Electric Ignition Systems
• Powerpile Systems
• NEW COMBUSTION TESTING DESIGN GAS EQUIPMENT
If you are interested in information
call 401-437-0557 or write to:
Gas Appliance Service Training and Consulting
22 Griffith Drive
Riverside, RI 02915
E-mail
gastc@cox.net

Air for
Combustion and Ventilation a New Subject - Part Two
March 2008 issue
by Tim
McElwain
After our
recent series on Venting and in particular “Special Venting” it is
also important to address the need for air for combustion and
ventilation. On many of my consulting calls I find that the
contractor or technician has overlooked the importance of insuring
adequate air for combustion. It is often the case that the homeowner
has done some remodeling and has overlooked the fact that what was
once a full open basement is now cut in half or even worse the
boiler or furnace along with the water heater are now in a small
tightly confined space with absolutely no provision for air.
Indoor Combustion Air
The required
volume of indoor air shall be determined in accordance with the
Standard Method or the Known Air Infiltration Rate Method except
that where the air infiltration rate is known to be less than ACH;
the KAIR method shall be used. The total required volume shall be
the sum of the required volume calculated for all appliances located
within the space. Rooms communicating directly with the space in
which the appliances are installed through openings not furnished
with doors, and through combustion air openings sized and located in
accordance with Indoor Opening Size and Location are considered a
part of the required volume.
The Standard Method has been in the code since the 1950s and remains
unchanged. It is limited to buildings with an air infiltration rate
of 0.4 air changes per hour (ACH) or more. A new method has been
added to the 2002 code, KAIR Method, which can be used to calculate
the required indoor volume for all structures, including those built
with very low air infiltration rates.
The code does not require the determination of the structure's air
infiltration. The Standard Method can be used for many
installations. However, if the structure's ACH is known to be less
than 0.40 ACH, then the Standard Method for obtaining combustion air
cannot be used, and the KAIR Method must be used.
It may be difficult to determine air infiltration in many cases. The
National Fuel Gas Handbook has a procedure in Supplement 5, which is
patterned after the ASHRAE Method. Another alternative based on
building blue prints could be used. There could also be a
pressurization test conducted, it is commonly called “a blower-door
test.” ASHRAE standard 62 recommends that buildings have a 0.35 air
change with at least 15 CFM per person.
IS THERE ENOUGH AIR FOR COMBUSTION?
This is the real question and sadly the need for air in the
equipment room is sadly overlooked. It is assumed that infiltration
air will take care of the requirements of the equipment. The area in
which the equipment is located must be -measured and calculations
made to determine if there is enough air for combustion.
The immediate need is to determine if there enough air for
combustion. A simple in house test can be conducted to determine
adequate air for equipment operation. It is a step-by-step process
as follows:
1. In as
much as is practical close all doors, windows etc. into the
space in which the equipment is located.
2. Bring on all the equipment in the house, which has a fan
operation such as clothes dryer, range hoods, exhaust fans,
bathroom fans, attic fans to operate at maximum speed.
3. Close the fireplace damper.
4. Bring on the boiler or furnace in question. The equipment
should be operating at peak efficiency no floating flames or
flashback. If the equipment is a two-stage gas furnace or boiler
bring it on to high fire.
5. Test for spillage of flue products at the draft hood of the
equipment. This can be done with a draft gauge, flame from a
match or candle, or smoke from a cigarette, cigar or pipe.
6. Bring on all the other fuel gas burning equipment within the
area of the boiler or furnace to full input and recheck at draft
hoods of all the equipment for spillage.
7. Return all equipment, doors windows etc. to normal position.
If you have a question as to whether sufficient air is being
supplied this test should assist you in determining if the
requirements for air for the equipment installed are being met.
When an appliance is located in a confined space Figure 3
illustrates some of the things that must be considered.
STANDARD METHOD
UNCONFINED SPACES
Unconfined
spaces will normally have enough natural infiltration of air. If the
construction is unusually tight, air from outdoors will be needed.
The minimum dimension of rectangular air ducts shall not be less
than 3 inches. The screening to cover the openings to the outside
shall not be less than 1/4 inch mesh and shall not be capable of
closure. Insect screening and louvers reduce effective area. In
calculating the free area of air openings, consideration must be
given to the blocking effect of louvers and grilles. If the free
area through a design of louver or grille is known, it should be
used in calculating the size opening required to provide the free
area specified. If the design and free area is not known, it may be
assumed that wood louvers will have a 20 to 25 percent free area and
metal louvers and grilles will have a 60 to 75 percent free area.
The louvers and grilles must be fixed in the open position or
interlocked with the equipment so that they are opened automatically
during equipment operation. The return air, circulating for
reheating by the furnace should be isolated from the air supply
coming from outside thru these ducts. In other words you cannot get
your air for combustion and return air for the furnace from the same
room. This will be covered in detail later. Let us look at an
example of how calculations may be applied.
PROBLEM:
RANCH HOUSE 25' X 40' with cellar ceiling 8' high 40 x 25 x 8 =
8,000 cubic feet of space
NATIONAL FUEL GAS CODE: 50 cubic feet of air for every 1,000
btu's
8000
50 = 160 x 1,000 = 160,000 btu's
House Heater = 100,000 Btu's
Water Heater = 35,000 Btu's
Dryer = 30,000
Btu's
165,000 btu’S
For
all practical purposes because the Btu's exceed 160,000 this
is a CONFINED SPACE and air must be brought from outdoors.
EQUIPMENT LOCATED IN UNCONFINED SPACES
Equipment
located in buildings of unusually tight construction shall be
provided air for combustion, ventilation, and dilution of flue gases
using the methods described. An unconfined space, which is shown in
Figure 5, is defined as follows:
Space, Unconfined. For purposes of the code, a space whose volume
is not less than 50 cubic feet per 1,000 Btu/hr of the aggregate
(sum total) input rating of all appliances installed in that space.
Rooms communicating directly with the space, in which the appliances
are installed, through openings not furnished with doors, are
considered a part of the unconfined space.
THIS Requirement IS SOMETIMES REFEREED TO AS THE 1/20 RULE, BECAUSE
1000 BTU/HR DIVIDED BY 50 CUBIC FEET OR, FOR EACH CUBIC FOOT OF ROOM
VOLUME, YOU CAN INSTALL 20 BTU/HR.
The requirement for additional air for combustion, ventilation, and
dilution recognizes that the definition of confined space came from
research on buildings of normal construction tightness. When
unusually tight construction is used, additional air is usually
required, and the code provides guidance to local code authorities
for determining when outside combustion and ventilation air is
necessary. In Figure 5 with 8,000 cubic feet of space this would
allow up to 160,000 Btu's before the space would be considered
confined. Therefore, there is no requirement for outside air. It is
important to remember to check for negative pressure caused by
mechanical exhausting, fans, fireplaces, clothes dryers, bathroom
fans, kitchen range or oven hoods, attic fans and any other fans in
the building etc. If you have negative pressure then additional air
will be required.

AIR FOR
COMBUSTION
ROOM SIZE:
LENGTH _____
WIDTH _____ HEIGHT _____
TOTAL _____
CUBIC FEET
Mechanical
Code is 40 cubic feet per 1,000 Btu's
National
Fuel Gas Code is 50 cubic feet per 1,000 Btu's
CUBIC FEET = X 1,000
40
CUBIC FEET = X 1,000
50
MAXIMUM BTU PER SPACE _____
IF THE AMOUNT OF BTU'S PER SPACE IS GREATER THAN THIS AMOUNT THEN IT
IS A CONFINED SPACE
TABLE 1

WORKSHEET
1

In
unconfined spaces in buildings of other than unusually tight
construction infiltration can be adequate to provide air for
combustion, ventilation and dilution of flue gases.
It was
however necessary to add item (4) to the 1999 code (4) the
building has an average air infiltration of less than 0.35 air
changes per hour. The concept of providing additional air to an
unusually tight building was first introduced in 1974. In 1988 a
definition was added. Since that time it can be considered normal in
most new residential construction. It has become apparent in recent
years that problems exist with combustion air obtained through
relying on infiltration air. It was important therefore to add the
air change per hour criteria to provide guidance when it is
determined that a building contains the first three construction
details. There may however still be enough air through infiltration
to provide combustion air. This recognizes that there may be enough
combustion air available due to the features of a buildings design
and construction. The amount of air may be affected by the design of
windows and doors in the building and how well the building is
constructed. We know that air infiltration of a building occurs
mainly as a result of pressure differences caused by winds on the
building or on the building interior being at a lower pressure than
the atmosphere. The temperature inside the building also affects it.
The air change rate of 0.35 was selected to correspond to the
definition of an unconfined space (50 cubic feet per 1000 Btu/hr),
which is known to provide sufficient air for combustion and
ventilation. This is illustrated in Figure 6 air infiltration and
construction type.

We are
now offering our latest manuals Circuitry and Troubleshooting Volume
I and Volume II. They are selling for $75.00 for Volume I and $35.00
for Volume II + $10.00 shipping and handling.
We have two OTHER NEW manuals in their second printing. The first
one is titled FUNDAMENTALS OF GAS VOLUME I it is priced at $75.00 a
copy + $10.00 shipping and handling. In addition we also have
FUNDAMENTALS OF GAS Volume II, which covers “Air for Combustion” and
“Venting” it is up to date with the latest changes to the Fuel Gas
Code Book. It is also being offered at a price of $75.00 + $10.00
shipping and handling.
We also conduct seminars on the following topics and many others:
|